Applications of the F-I/O module

5.3 Application 2: Safety mode SIL3/Cat.3/PLe

5.3
Application 2: Safety mode SIL3/Cat.3/PLe
Assigning inputs to each other
The digital input module F-DI 8×24VDC HF has 8 fail-safe inputs, DI
combine two of these inputs each to one input.
You can combine the following inputs:
• DI
• DI
• DI
• DI
The process signals are provided by channels DI
Wiring
The wiring is carried out on the matching BaseUnit.
Sensor supply
The sensor supply can be internal or external.
Wiring diagram - connecting a two-channel sensor equivalent via two channels
Per process signal, a two-channel sensor is connected equivalent via two channels to two
inputs of the F-module (1oo2 evaluation).
Any sensor supply of the module can be assigned to each input.
You can also supply the sensor by means of an external sensor supply.
42
and DI
0
4
and DI
1
5
and DI
2
6
and DI
3
7
, DI
, DI
and DI
.
0
1
2
3
Digital input module F-DI 8x24VDC HF (6ES7136-6BA01-0CA0)
Equipment Manual, 10/2021, A5E50578307-AA