x = Sensor supply
T1x = Time for short-circuit test
T2x = Startup time of sensor after short-circuit test
n = Number of sensor supplies with activated short-circuit test
The following section provides two examples for the calculation of the maximum response
time to external short-circuits at an F-DI 8×24VDC HF, depending on the parameter
assignment.
Channe
Input delay
Short-circuit
l
(ms)
test
0
3.2
Enable
1
3.2
Enable
2
3.2
Enable
3
3.2
Enable
4
3.2
Enable
5
3.2
Enable
6
3.2
Enable
7
3.2
Enable
Example calculation: (4.2 ms + 4.2 ms) >= 8.0 ms→ Ts = max (4.2 ms, 8.0 ms) + 4.2 ms =
12.2 ms
Chann
Input delay
Short-circuit
el
(ms)
test
0
0.4
Enable
1
0.8
Enable
2
1.6
Enable
3
3.2
Enable
4
0.4
Disable
5
0.8
Enable
6
1.6
Enable
7
3.2
Enable
*) External short-circuits are not detected with a deactivated short-circuit test.
Example calculation channel 1: (4.2 ms +10 ms) >= 8.0 ms → Ts = max (4.2 ms, 8.0 ms) +
10 ms = 18.0 ms
Digital input module F-DI 8x24VDC HF (6ES7136-6BA01-0CA0)
Equipment Manual, 10/2021, A5E50578307-AA
T1
T2
T
cycle
(ms)
(ms)
(ms)
4.2
4.2
8.0
4.2
4.2
8.0
4.2
4.2
8.0
4.2
4.2
8.0
4.2
4.2
8.0
4.2
4.2
8.0
4.2
4.2
8.0
4.2
4.2
8.0
T1
T2
T
cycle
(ms)
(ms)
(ms)
0.5
0.5
8.0
4.2
10
8.0
20
4.2
8.0
100
100
8.0
-
-
8.0
4.2
4.2
8.0
500
500
8.0
2000
2000
8.0
T1 + T2 <
Ts (ms)
T
cycle
NO
12.2
NO
12.2
NO
12.2
NO
12.2
NO
12.2
NO
12.2
NO
12.2
NO
12.2
T1 + T2 <
Ts (ms)
T
cycle
YES
8.0
NO
18.0
NO
24.2
NO
200
-
-
NO
12.2
NO
1000
NO
4000
Response times
Max. response time to
external short-circuits
(ms)
172.8
172.8
172.8
172.8
172.8
172.8
172.8
172.8
Max. response time to
external short-circuits
(ms)
5334.8
5335.2
5336.0
5337.6
- *)
5335.2
5336.0
5337.6
71