Number Of Signal Changes; Monitoring Window; Address Space - Siemens SIMATIC ET 200SP Equipment Manual

Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

4.2.4.6

Number of signal changes

Defines the number of signal changes after whose sequence a chatter error is to be reported.
4.2.4.7

Monitoring window

Sets the time for the monitoring window of chatter monitoring.
You can set times of 1 s to 100 s in whole seconds for the monitoring window.
If you parameterize 0 s, the monitoring window is 0.5 s long.
4.3

Address space

Address assignment of the digital input module F-DI 8×24VDC HF
The digital input module F-DI 8×24VDC HF occupies the following address areas in the F-CPU:
Table 4- 2
F-CPU
F-CPUs S7-300/400
F-CPUs S7-1200/1500
x = Module start address
Digital input module F-DI 8x24VDC HF (6ES7136-6BA01-0CA0)
Equipment Manual, 10/2021, A5E50578307-AA
Address assignment in the F-CPU
Occupied bytes in the F-CPU:
In input range
IB x + 0 to x + 5
IB x + 0 to x + 6
Parameters/address space
4.3 Address space
In output range
QB x + 0 to x + 3
QB x + 0 to x + 4
35