Diagnostic message
Parameter F_CRC_Length
does not match the
generated values
Version of F parameter set
incorrect
CRC1 fault
Device-specific diagnostics
information, see manual
Inconsistent iParameter
(iParCRC error)
F_Block_ID not supported
Transmission error:
Inconsistent data (CRC error)
Transmission error: Timeout
(watchdog time 1 or 2
expired)
Acknowledge required to
enable channel(s) - as
channel error(s) are
remedied.
Watchdog tripped
Invalid/inconsistent firmware
present
Digital input module F-DI 8x24VDC HF (6ES7136-6BA01-0CA0)
Equipment Manual, 10/2021, A5E50578307-AA
Fault
Meaning
code
45
The PROFIsafe driver has detected a
H
discrepancy in the CRC length.
46
The PROFIsafe driver has detected an
H
incorrect version of the F-parameters or
an invalid F_Block_ID.
47
The PROFIsafe driver has detected
H
inconsistent F-parameters.
48
The PROFIsafe driver has received
H
inconsistent fail-safe parameters.
4B
The PROFIsafe driver has detected
H
inconsistent iParameters.
4C
The PROFIsafe driver has detected an
H
incorrect Block ID.
4D
The PROFIsafe driver has detected a CRC
H
error.
Possible causes:
The communication between F-CPU
and F-module is interrupted.
Impermissibly high electromagnetic
interference is present.
An error has occurred during the sign-
of-life monitoring.
4E
The PROFIsafe driver has detected a
H
timeout.
Possible causes:
The F-monitoring time is set
incorrectly.
A bus fault is present.
4F
A channel fault was detected. A
H
confirmation is required to enable the
channel.
103
Possible causes:
H
An impermissibly high
electromagnetic interference is
present.
The F-module has detected an internal
error and reacted to it in a safety-
oriented manner.
11B
The firmware is incomplete and/or
H
firmware added to the F-module is
incompatible. This leads to errors or
functional limitations when operating the
F-module.
Interrupts/diagnostic messages
6.3 Diagnostic messages
Remedy
Check the parameter assignment of the
PROFIsafe driver.
Check the parameter assignment of the
PROFIsafe driver.
Check the communication link
between the F-module and the F-
CPU.
Eliminate the cause of the
electromagnetic interference.
Check the parameter assignment.
Make sure that your
communication is operating
correctly.
Confirm the channel fault.
Correct the fault. The module must
then be pulled and plugged, or the
power switched OFF and ON.
If the F-module cannot be put into
operation anymore, consider a
replacement.
Perform a firmware update for all
parts of the F-module and note any
error messages.
Use only firmware versions released
for this F-module.