Article number
•
•
•
•
Potential separation
Potential separation channels
•
•
•
Isolation
Isolation tested with
Standards, approvals, certificates
Suitable for safety functions
Highest safety class achievable in safety mode
•
•
•
Probability of failure (for service life of 20
years and repair time of 100 hours)
Ambient conditions
Ambient temperature during operation
•
•
•
•
Altitude during operation relating to sea level
•
Dimensions
Width
Height
Depth
Weights
Weight, approx.
Digital input module F-DI 8x24VDC HF (6ES7136-6BA01-0CA0)
Equipment Manual, 10/2021, A5E50578307-AA
Monitoring of the supply voltage (PWR-LED)
Channel status display
for channel diagnostics
for module diagnostics
between the channels
between the channels and backplane bus
between the channels and the power supply
of the electronics
Performance level according to ISO 13849-1
Category according to ISO 13849-1
SIL acc. to IEC 61508
Low demand mode: PFDavg in accordance
–
with SIL3
High demand/continuous mode: PFH in
–
accordance with SIL3
horizontal installation, min.
horizontal installation, max.
vertical installation, min.
vertical installation, max.
Installation altitude above sea level, max.
Technical specifications
6ES7136-6BA01-0CA0
Yes; green PWR LED
Yes; green LED
Yes; red LED
Yes; green/red DIAG LED
No
Yes
No
707 V DC (type test)
Yes
PLe
Cat. 4
SIL 3
< 2.00E-05
< 1.00E-09 1/h
0 °C
60 °C
0 °C
50 °C
4 000 m; restrictions for installation altitudes > 2
000 m, see ET 200SP system manual
15 mm
73 mm
58 mm
29 g