The safety parameters in the technical data apply for a mission time of 20 years and a repair
time of 100 hours. If a repair within 100 hours is not possible, remove the respective
module from the BaseUnit or switch off its supply voltage before 100 hours expires.
Proceed for the repair as described in the section Diagnostics messages.
Accessories
You can order the following accessories separately:
• Labeling strips
• Color identification labels
• Reference identification labels
• Shield connection
• Electronic coding element as replacement part (part number 6ES7193-6EF00-1AA0)
For more information on accessories, refer to the system manual ET 200SP Distributed I/O
System (https://support.industry.siemens.com/cs/ww/en/view/58649293).
Digital input module F-DI 8x24VDC HF (6ES7136-6BA01-0CA0)
Equipment Manual, 10/2021, A5E50578307-AA
WARNING
Product overview
2.1 Properties