Extended Ethernet Settings for PROFINET [B1, B2]

If the PDM MS is connected directly to several Ethernet bus systems, an additional
IP address must be added in the network settings.
This is the case, for example, when the PDM MS is connected to the plant bus and
also directly connected (via switch/service bridge) to a PROFINET fieldbus, or
when connected to several PROFINET fieldbuses.
Figure 5-2
S7-CPU or
3rd party PLC
PN Fieldbus
Network 1
1. Open the PDM MS Network Settings.
2. Open the Network Setting Properties of the LAN #02 port.
(The LAN #01 port is usually reserved for the terminal bus.)
PDM Maintenance Station
Entry ID: 109776936,
V1.0,
S7-CPU or
3rd party PLC
PN Fieldbus
Network 2
PROFIBUS PA
02/2020
SIMATIC PDM
Maintenance Station
Service
Bridge
S7- 410H
PROFIBUS PA
PDM MS Adapter
„Plant Bus 1"
PROFIBUS DP
PA Link
PROFIBUS PA
ET 200M
HART
25