9 Engineering Steps for the Maintenance Station [all]
9.2

AS/OS Configuration for the PDM Maintenance Station

To enable the runtime function of the PDM MS, the following steps must be
performed.
1. Right-click the project in the Plant hierarchy and select "Insert new object >
Hierarchy folder" from the context menu.
2. Select the menu command Tools > Plant Hierarchy > Settings.
3. Check the box for the function "Derive picture hierarchy from the plant
hierarchy" and select "Maintenance Station PDM (no AS diagnostics)".
Figure 9-2
4. After clicking "OK", the basic folders for the Diagnostics hierarchy are created.
Figure 9-3
PDM Maintenance Station
Entry ID: 109776936,
V1.0,
02/2020