Figure 3-23 External EMC filter (size 5 to 6)
Y
V
W
C
Y
D
E
Y
V: Ground stud
Z: Bookcase mounting slot diameter. CS: Cable size
Table 3-8 Size 5 external EMC filter dimensions
CT part
A
number
4200-0312
4200-0402
395 mm
(15.55 in)
4200-0122
Table 3-9 Size 6 external EMC filter dimensions
CT part
A
number
4200-2300
392 mm
4200-4800
(15.43 in)
(16.54 in)
4200-3690
3.11.3
EMC filter torque settings
Table 3-10 Optional external EMC Filter terminal data
CT part
number
4200-0122
4200-0312
4200-0402
4200-2300
4200-4800
4200-3690
44
X
X: Threaded holes for footprint
mounting of the drive
B
C
D
425 mm
106 mm
60 mm
(16.73 in)
(4.17 in)
(2.36 in)
B
C
D
420 mm
180 mm
60 mm
(7.09 in)
(2.36 in)
Power
connections
Max cable
size
2
1.8 N m (1.4 lb ft)
6 mm
(8 AWG)
2
1.8 N m (1.4 lb ft)
6 mm
(8 AWG)
2
1.8 N m (1.4 lb ft)
6 mm
(8 AWG)
2
2.3 N m (1.70 Ib ft)
16 mm
(6 AWG)
2
2.3 N m (1.70 Ib ft)
16 mm
(6 AWG)
2
2.3 N m (1.70 Ib ft)
16 mm
(6 AWG)
A
B
H
E
H
33 mm
437 mm
(1 30 in)
(17.2 in)
E
H
33 mm
434 mm
(1.30 in)
(17.09 in)
Max torque
Ground stud size
Unidrive M/HS Frame 5 to 6 Power Installation Guide
Z
Z
Z
Y: Footprint mounting hole diameter
W
V/X
Y/Z
143 mm
6.5 mm
M6
(5.63 in)
(0.26 in)
W
V/X
Y/Z
210 mm
6.5 mm
M6
(8.27 in)
(0.26 in)
Ground
connections
Max torque
M6
5.0 N m (3.7 lb ft)
M6
5.0 N m (3.7 lb ft)
M6
5.0 N m (3.7 lb ft)
M6
5.0 N m (3.7 lb ft)
M6
5.0 N m (3.7 lb ft)
M6
5.0 N m (3.7 lb ft)
Issue Number: 8
CS
CS
2
10 mm
(8 AWG)
2
2.5 mm
(14 AWG)
CS
2
16 mm
(6 AWG)

Hide quick links: