5.1.24
Torque settings
Table 5-26 Drive control and relay terminal data
Model
All
Table 5-27 Drive power terminal data
AC and motor terminals
Frame
size
Recommended
Plug-in terminal block
5
1.5 N m
(1.1 lb ft)
M6 Nut (10 mm AF)
6
6.0 N m
(4.4 Ib ft)
Table 5-28 Plug-in terminal block maximum cable sizes
Frame size
11 way control connectors
All
2 way relay connector
3 way AC power connector
5
3 way motor connector
2 way low voltage power
6
24 V supply connector
Table 5-29 External EMC filter terminal data
CT part
number
Max cable
4200-0122
16 mm
4200-0312
(6 AWG)
4200-0402
4200-2300
16 mm
4200-4800
(6 AWG)
4200-3690
100
Connection type
Plug-in terminal block
Maximum
Recommended
M4 Nut (7 mm AF)
1.8 N m
1.5 N m
(1.3 lb ft)
(1.1 Ib ft)
M6 Nut (10 mm AF)
8.0 N m
6.0 N m
(6.0 Ib ft)
(4.4 Ib ft)
Terminal block description
Power
connections
Max torque
size
2.3 N m
(1.7 lb ft)
2
1.8 N m
(1.4 lb ft)
2
2.3 N m
(1.70 Ib ft)
DC and braking
Maximum
T20 Torx (M4) /
2.5 N m
(1.8 Ib ft)
8.0 N m
(6.0 Ib ft)
Ground stud size
M6
Unidrive M/HS Frame 5 to 6 Power Installation Guide
Torque setting
0.5 N m (0.4 lb ft)
Ground terminal
Recommended
Maximum
M5 Nut (8 mm AF)
2.0 N m (1.4 Ib ft)
5.0 N m (3.7 Ib ft)
M6 Nut (10 mm AF)
6.0 N m(4.4 Ib ft)
8.0 N m (6.0 Ib ft)
Max cable size
2
1.5 mm
(16 AWG)
2
2.5 mm
(12 AWG)
2
8 mm
(8 AWG)
2
1.5 mm
(16 AWG)
Ground
connections
Max torque
4.8 N m
(2.8 lb ft)
Issue Number: 8
Need help?
Do you have a question about the Commander C200 and is the answer not in the manual?