Main circuit terminals

2.5.1
Details on the main circuit terminals of the
inverter
Terminal
Terminal name
symbol
U, V, W
Inverter output
R1/L11,
Power supply for the control
S1/L21
circuit
P/+, N/-
Converter unit connection
Earth (ground)
2.5.2
Details on the main circuit terminals of the
converter unit (FR-CC2)
Terminal
Terminal name
symbol
R/L1,
S/L2,
AC power input
T/L3
R1/L11,
Power supply for the control
S1/L21
circuit
P/+, N/-
Inverter connection
Earth (ground)
Terminal function description
Connect these terminals to a three-phase squirrel cage motor or a PM motor. -
Connected to terminals P/+ and N/-. To retain the fault display and fault
output, or to use the converter unit (FR-CC2), remove the jumpers installed
across terminals R1/L11 and S1/L21, and supply external power to these
terminals.
The power capacity necessary when separate power is supplied from
terminals R1/L11 and S1/L21 is 80 VA.
Connect the converter unit (FR-CC2).
For earthing (grounding) the inverter chassis. This must be earthed
(grounded).
Terminal function description
Connect these terminals to the commercial power supply.
Connected to the AC power supply terminals R/L1 and S/L2. To retain the
fault display and fault output, remove the jumpers across terminals R/L1 and
R1/L11 and across S/L2 and S1/L21, and supply external power to these
terminals.
When using a separate power supply from R1/L11 and S1/L21, the
necessary power capacity of the separate power supply is 80 VA.
Connect to terminals P/+ and N/- of the inverter.
For earthing (grounding) the converter unit chassis. Be sure to earth (ground)
the converter.
Main circuit terminals
INSTALLATION AND WIRING
Refer
to page
41
25
31
Refer
to page
-
41
25
31
2
27