Mitsubishi Electric FR-A862-E Instruction Manual page 75

Hide thumbs Also See for FR-A862-E:
Table of Contents

Advertisement

Inspection item
5.1.4
Checking the inverter and converter modules
Preparation
• Disconnect the external power supply cables (R/L1, S/L2, T/L3) and motor cables (U, V, W). (The inverter and the converter
unit (FR-CC2) can be measured with those cables connected.)
• Prepare a continuity tester. (For the resistance measurement, use the 100  range.)
Checking method
Change the polarity of the tester alternately at a semiconductor device (transistor) on an electrical path between two terminals
among the inverter main circuit terminals R/L1, S/L2, T/L3, U, V, W, P/+, and N/- to check the electric continuity.
NOTE
• Before measurement, check that the smoothing capacitor is discharged.
• At the time of electric discontinuity, the measured value is almost ∞. When there is an instantaneous electric continuity, due to
the smoothing capacitor, the tester may not indicate ∞. At the time of electric continuity, the measured value is several  to
several tens of . When all measured values are almost the same (although values may not be constant depending on the
tester type), it shows that there are no electrical paths with problems.
Device number and target terminal
Converter module
D1
D2
D3
R/L1
C
S/L2
T/L3
D4
D5
D6
Tester
polarity
R/L1,
P/+
D1
P/+
R/L1,
S/L2,
P/+
D2
P/+
S/L2,
T/L3
P/+
D3
P/+
T/L3
U
P/+
TR1
P/+
U
V
P/+
TR3
P/+
V
W
P/+
TR5
P/+
W
(Assuming that an analog meter is used.)
74
PRECAUTIONS FOR MAINTENANCE AND INSPECTION
Inverter module
P/+
P/+
TR1
C
TR4
N/-
N/-
Tester
polarity
Continuity
No
R/L1,
D4
Yes
N/-
R/L1,
No
S/L2,
D5
Yes
N/-
S/L2,
No
T/L3
D6
Yes
N/-
T/L3
No
U
TR4
Yes
N/-
No
V
TR6
Yes
N/-
No
W
TR2
Yes
N/-
TR3
TR5
U
V
W
TR6
TR2
Continuity
N/-
Yes
No
N/-
Yes
No
N/-
Yes
No
N/-
Yes
U
No
N/-
Yes
V
No
N/-
Yes
W
No