Mitsubishi Electric FR-A862-E Instruction Manual page 36

Hide thumbs Also See for FR-A862-E:
Table of Contents

Advertisement

Terminals for manufacturer setting
Terminal symbol
Terminals S1, S2, SIC, So (SO), and SOC are for manufacturer setting. Do not connect anything to there. Doing so
S1, S2, SIC, So
may cause an inverter failure.
(SO), SOC
Do not remove the shorting wires across terminals S1 and PC, terminals S2 and PC, and terminals SIC and SD.
Removing either shorting wire disables the inverter operation.
2.6.2
Details on the control circuit terminals of the
converter unit (FR-CC2)
The input signal function of the terminals in
function selection).
For the parameter details, refer to the Instruction Manual of the FR-CC2-C.
Input signal
Terminal
Terminal name
symbol
RES
Reset
External thermal
OH
relay input
RDI
Contact input
Contact input
common (sink)
External transistor
SD
common (source)
24 VDC power supply
common
External transistor
common (sink)
PC
Contact input
common (source)
24 VDC power supply
common
24 V external power
+24
supply input
Terminal function description
can be selected by setting Pr.178, Pr.187, Pr.189 to Pr.195 (I/O terminal
Terminal function description
Use this signal to reset a fault output provided when a protective function
is activated. Turn ON the RES signal for 0.1 second or longer, then turn it
OFF.
In the initial setting, reset is always enabled. By setting Pr.75, reset can
be set enabled only at fault occurrence of the converter unit. The inverter
recovers about 1 second after the reset is released.
The External thermal relay input (OH) signal is used when using an
external thermal relay or a thermal protector built into the motor to
protect the motor from overheating.
When the thermal relay is activated, the inverter is shut off due to the
fault occurrence of the external thermal relay operation (E.OHT).
The function can be assigned by setting Pr.178.
Common terminal for contact input terminal (sink logic) and terminal FM
Connect this terminal to the power supply common terminal of a
transistor output (open collector output) device, such as a programmable
controller, in the source logic to avoid malfunction by undesirable
current.
Common terminal for the 24 VDC power supply (terminal PC, terminal
+24)
Isolated from terminals 5 and SE.
Connect this terminal to the power supply common terminal of a
transistor output (open collector output) device, such as a programmable
controller, in the source logic to avoid malfunction by undesirable
current.
Common terminal for contact input terminal (source logic).
Can be used as a 24 VDC 0.1 A power supply.
For connecting a 24 V external power supply.
If a 24 V external power supply is connected, power is supplied to the
control circuit while the main power circuit is OFF.
Control circuit
Input resistance:
4.7 k
Voltage when
contacts are open: 21
to 27 VDC
Current when
contacts are short-
circuited: 4 to 6
mADC
———
Power supply voltage
range:
19.2 to 28.8 VDC
Permissible load
current: 100 mA
Input voltage:
23 to 25.5 VDC
Input current:
1.4 A or less
INSTALLATION AND WIRING