Ground the Front Door

Note
To comply with GR-1089, you have to bond the front doors to the ground port on the chassis using the ground
braid.
Procedure
Step 1
Install the grounding cable towards the side of the front door.
Step 2
Apply the star ring terminal end of the grounding cable to the front door. Tighten the screw to 11.5 to 15 in-lb
(1.3 to 1.7 N-m) of torque to provide proper bonding.
Figure 40: Ground Cable to Chassis
Note
Step 3
Connect the other round terminal of the grounding cable to the ground port on the cable management bracket
on either left or right side of the chassis. Use the front hole of the bracket that connects the top cover to the
cable management bracket. Tighten the M4 screw to 11.5 to 15 in-lb (1.3 to 1.7 N-m) of torque.
Step 4
Repeat Steps 1–3 to install the grounding cable to the other front door.
Install the following modules, if you had them removed from the chassis while mounting into the
rack.
• Fan trays
For more information on replacing components, see
Fasten the ground straps on both the doors to the chassis.
Install Power Shelf Bezel, on page
Replace a Fan
Hardware Installation Guide for Cisco 8800 Series Routers
Ground the Front Door
115.
Tray.
51

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

881888128808

Table of Contents