 Ethernet − Direct Connection
Sysmac Studio cannot connect
to the NA Unit.
Is power supplied to the
NA Unit?
Are the Ethernet cables
connected properly?
Is the connection method
set to a direct Ethernet connection in
the Communications Setup of the
Sysmac Studio?
Is the same IP address set
for more than one node (e.g.,
computer or NA Unit) in the same
domain?
Is the Ethernet cable
connected to the Ethernet interface card
that is specified to use to connect to the
NA Unit in the Sysmac Studio?
Replace the Ethernet cable.
NA-series Programmable Terminal Hardware(-V1) User's Manual (V125)
No
Turn ON the power supply to
the NA Unit .
Yes
No
Can the Sysmac Studio go online
Insert the cable connectors at the personal computer, Ethernet
No
switches, and the NA Unit until they lock into place. Verify that
the link indicator is lit at the computer and Ethernet switches,
and that the LINK/ACT indicator is lit at the NA Unit.
Yes
No
Can the Sysmac Studio go online
No
Set the connection method to a direct Ethernet connection in
the Communications Setup of the Sysmac Studio.
Yes
No
Can the Sysmac Studio go online
Set the IP address for the personal computer. Use
No
the default IP address for the NA Unit or connect
the Sysmac Studio to the NA Unit with a USB
cable and set the required IP address.
Yes
No
Can the Sysmac Studio go online
Change the Ethernet interface card specification
at the Sysmac Studio or connect the Ethernet
No
cable to the specified Ethernet interface card.
Refer to the appendices of the Sysmac Studio
Version 1 Operation Manual (Cat. No. W504) for
the procedure to specify the Ethernet interface
card.
Yes
No
Can the Sysmac Studio go online
Yes
with the NA Unit ?
Yes
with the NA Unit ?
Yes
with the NA Unit ?
Yes
with the NA Unit ?
Yes
with the NA Unit ?
5 Troubleshooting
END