8 Appendix A – Quick Setup
IMPORTANT: To properly and effectively program the system you must configure the Sensors, Relays, Zones, and Signals. If the user
has not entered any parameters, the system WILL NOT be monitoring the sensors or controlling the ventilation system. The relays will
be in the not actuated state and the horn and strobe outputs will be off. Be sure that the 4-20mA output on each sensor is set to "On".
Configure System
1.
custom sensors and change the password.
Configure Sensors
2.
Alarm Level, Warning Level, and Sensor Range
Configure Relays
3.
to all three relays as well as the horn and strobe.
Note: The Delay Time default is 1 minute. If the duration of a test procedure or gas exposure is less than 1 minute, the relays,
horns, and strobes may not engage even though the DVP-120 display and the sensors respond. When testing the system
disable the delay (set Delay Time to zero minutes/seconds).
Configure Zones
4.
type and output within the same zone) - Sensor type, Sensor Number, Rising Trip point and Falling Trip point
Configure Signals
5.
Intermittent, Continuous, etc.
Note 1: The default Password is 1234. If the password has been changed and/or lost:
o Power down the unit. Remove the Jumper Shorting Connector from the EXT header and place it on the top two pins
of the SYS header.
o Power up the DVP-120. The first display is the current password on the unit.
o Power down the unit. Remove the Jumper Shorting Connector from the SYS header and place it back onto the two
bottom pins of the EXT header.
Note 2: When entering multiple digit values the Up arrow ( ) acts as an enter key and it is not necessary to enter all allowed fields.
Any other key is ignored or cancels the current parameter change.
Note 3: The MENU key will cause the system to shift to the Configuration Menu. The up and down and left and right arrow keys will
scroll through all configuration parameters.
Default Configuration:
• Password
• Sensors
• Alarm signals
• Warning signals
• Trouble signals
• Relay 1
• Relay 2
• Relay 3
• Horn
• Strobe
• Zone1
• Zone2
• Zone3
• Group 1 in each zone
; allows the installer to set the time of day, the day of the week, load the default configuration, configure
; defines the Sensor type – CO, NO
, Horn and Strobe: defines operation as Normally Off or On, Delay Time, Minimum Runtime – this applies
: defines Sensor Input & Relay/Alarm Output and sets up the sensor Groups (set of sensors of the same
: defines the output of the Alarm, Warning and Trouble Signals (Buzzer, Horn and Strobe) as On, Off,
1234
Undefined
Buzzer = Intermittent, Horn = Intermittent, Strobe = Continuous
Buzzer = Off, Horn = Off, Strobe = Off
Buzzer = Triple Tap, Horn = Off, Strobe = Off
Normally off, 1-minute turn on delay, 1 minute minimum on time
Normally off, 1-minute turn on delay, 1 minute minimum on time
Normally off, 1-minute turn on delay, 1 minute minimum on time
Normally off, 1-minute turn on delay, 0 (zero) minimum on time
Normally off, 1-minute turn on delay, 0 (zero) minimum on time
Controls R1
Controls R2
Controls R3
Type 1 CO, Voting mode, Quorum = 1
, EX, NH
, H
S, REF, CO
, O
2
3
2
2
50
, Custom (wildcard) or None and sets
2