13. Zone 3
14. Group 1 in each zone
15. Group 2 in each zone
16. Group 3 in each zone
17. Group 4 in each zone
18. Group 5 in each zone
19. Group 6 in each zone
20. Group 7 in each zone
21. Group 8 in each zone
22. Group 9 in each zone
Carbon
Description
Monoxide
Type
CO
Range
200ppm
Alarm Level
200ppm
Warning
100ppm
Level
Rising Level
35ppm
Falling Level
15ppm
4.3.2.4
Change Password
When the first digit is entered to change the password, the panel will prompt for the existing password to be entered (if it hasn't already
been entered), see section
for the new password.
4.3.2.5
Configure sensor Type
Sensor Registration
Sensor registration is continuously monitored by the DVP-120. When the currently selected sensor type agrees with the stored registration
information the DVP-120 will remain in normal mode. When new registration information is detected by the DVP-120, for example, if a
different gas type of Macurco sensor was installed, the following message is displayed: "Configuration Changed Any key to save" is
displayed.
Pressing any key will prompt the user to enter the password. Once the valid password is entered the new sensor type is saved. The
program does not allow any other activity unless a valid password is entered.
If the DVP-120 is in configuration mode (user is changing the configuration) the registration information is saved in the background and
the message indicating that configuration was changed is delayed until the user goes back to normal mode.
Controls R3
Type 1 CO, Voting mode, Quorum = 1
Type 2 NO
Type 3 EX, Voting mode, Quorum = 1
Type 4 NH
Type 5 H
2
Type 6 REF, Voting mode, Quorum = 1
(Currently not used)
Type 8 O
2
Type 9 CO
Nitrogen
Combustible
Dioxide
Gas
NO
EX
2
20ppm
50% LEL
5ppm
20% LEL
3ppm
15% LEL
2.5ppm
10% LEL
1.2ppm
5% LEL
Figure 4-22 Default Configuration Settings
C h a n g e
Figure 3-23 Change Password
4.3.2.6 Enter Password
for more detail. Once the current password has been entered, the panel will prompt
Config.
Any
Figure 4-23.1 Configuration Changed
, Voting mode, Quorum = 1
2
, Voting mode, Quorum = 1
3
S, Voting mode, Quorum = 1
, Voting mode, Quorum = 1
Voting mode, Quorum = 1
2
Hydrogen
Ammonia
Sulfide
NH
H
3
100ppm
50ppm
75ppm
20ppm
50ppm
14ppm
25ppm
8ppm
10ppm
3ppm
P a s s w o r d
* * * *
changed
Key
to
save
26
Carbon
Refrigerants
Dioxide
S
REF
2
1000ppm
5,000ppm
300ppm
4,000ppm
200ppm
1,500ppm
100ppm
1,000ppm
50ppm
800ppm
Oxygen
CO
O
2
2
25% v/v
19.5% v/v
20.0% v/v
20.3% v/v
20.6% v/v