• 9
Carbon Dioxide (CO
The default Types are:
Group 1 in each zone
Group 2 in each zone
Group 3 in each zone
Group 4 in each zone
Group 5 in each zone
Group 6 in each zone
Group 7 in each zone
Group 8 in each zone
Group 9 in each zone
Timed mode turns the zone's outputs on at the START TIME if the current day is a weekday (or a weekend) and turns them off at the
next occurrence of STOP TIME. The other three modes turn the outputs on if the gas concentration indicated by that type of sensor is at
or above the Rising Trip Point and turns the outputs off if the concentration is less than or equal to the Falling Trip Point.
4.3.7.3
Timed Day Selection
Valid entries are:
1. 1 Weekdays, Monday thru Friday, (default)
2. 2 Weekends, Saturday and Sunday
4.3.7.4
Start Time
The start time is entered in 24-hour format and the default value is 07:00 (7:00 AM).
4.3.7.5
Stop Time
The stop time is entered in 24-hour format and the default value is 18:00 (6:00 PM).
4.3.7.6
Sensor Selection
)
2
Type 1 CO, Voting mode, Quorum = 1
Type 2 NO
, Voting mode, Quorum = 1
2
Type 3 EX, Voting mode, Quorum = 1
Type 4 NH
, Voting mode, Quorum = 1
3
Type 5 H
S, Voting mode, Quorum = 1
2
Type 6 REF, Voting mode, Quorum = 1
(currently unused)
Type 8 O
, Voting mode, Quorum = 1
2
Type 9 CO2, Voting mode, Quorum = 1
Z 1
G r o u p
D a y s : 1
Figure 4-42 Timed Day Selection
Z 1
G r o u p
S t a r t
T i m E : 0 7 : 0 0
Figure 4-43 Start Time Selection
Z 1
G r o u p
S t o p
T i m e :
Figure 4-44 Stop Time Selection
Z 1
G r o u p
S e n s o r s : 0 2 , 0 4 , 1 1
Figure 4-45 Sensor Selection
1
T i m e d
W E e k d a y s
1
T i m e d
1
T i m e d
1 8 : 0 0
1
N O 2
35