Macurco DVP-120B User Instructions page 28

Detection and ventilation control panel
Table of Contents

Advertisement

"Res." Defines the resolution used to display the reading, alarm, warning, range, falling level and rising level. It can have values between
1 and 500 when "Dec." is 0, 50.0 when "Dec." is 1 and 5.00 when "Dec." is 2.
"Range" is the value displayed when current measured is 20mA.
"Alarm" is the default alarm range.
"Warn" is the default warning range.
"Rise" is the default rising level used in Zone configuration.
"Fall" is the default falling level used in Zone configuration.
For the custom sensor, types default parameters are set to display the current measured above 4 mA. So if the current is 4 mA, it displays
0.00 mA. And when the current is 20 mA it displays 16.00 mA.
4.3.2.6
Enter Password
If the password has not yet been entered, when the first digit of any parameter is entered, the panel will prompt for the current password.
Note that the first digit entered is discarded; it does not count toward the password or toward the parameter entry.
Type: 01
Res.:
1 ppm
Figure 4-23.8 Resolution
Type: 01
Range:
200 ppm
Figure 4-23.9 Sensor Range
Type: 01
Alarm:
200 ppm
Figure 4-23.10 Alarm Level
Type: 01
Warn:
100 ppm
Figure 4-23.11 Warning Level
Type: 01
Rise:
35 ppm
Figure 4-23.12 Rising Trip Point
Type: 01
Fall:
15 ppm
Figure 4-23.13 Falling Trip Point
28
CO
CO
CO
CO
CO
CO