4.3.3.5
Range
The range for each sensor is the gas concentration that corresponds to the 20-mA signal level.
The default range values for the sensors are:
Carbon
Description
Monoxide
Range
200ppm
4.3.4
Configure Relays, Horn & Strobe Submenu
There is a list of parameters for each relay in the system. The left and right cursor keys can be used to move from one relay, horn or
strobe to another and the up and down keys will scroll through the parameters for the particular relay, horn or strobe.
4.3.4.1
Relay Summary
This display example shows that Relay 1 is configured to operate Normally Off, with a turn-on delay and a minimum on time.
Notice that the relay number, 1 in this example, is underlined. This indicates that the digit keys can be used to jump to a particular relay,
horn or strobe. The relays are numbers 1, 2 and 3; the horn is number 4 and the strobe is 5.
4.3.4.2
Relay Mode
This display example shows that relay 1 is configured to operate in the Normally Off mode. The relay modes are:
1
ALARM
2
Normally Off (default)
3
Normally On
Relay mode 1 is a special case. This mode is only available on relay 1 and dedicates the relay to function as an alarm signal to a
subsequent alarm or monitoring panel. This mode forces the relay to Normally Off mode with no turn on delay or minimum on time. See
Section 4.1.7 for more detail regarding alarms.
S e n s o r
R a n g e :
Figure 4-29 Sensor Range
Nitrogen
Combustible
Dioxide
Gas
20ppm
50% LEL
R e l a y
1
D e l a y
O n , M i n . O n
Figure 4-30 Relay Summary
R e l a y
1
M o d e : 2
Figure 4-31 Relay Mode
0 1
C O
2 0 0 p p m
Hydrogen
Ammonia
Sulfide
100ppm
50ppm
N o r m . O f f
N o r m . O f f
31
Carbon
Refrigerants
Dioxide
1,000ppm
5,000ppm
Oxygen
25% v/v