Operation; Maintenance; Repair; Modification - Endress+Hauser Proline Prosonic Flow P 500 Functional Safety Manual

Ultrasonic time-of-flight flowmeter hart
Hide thumbs Also See for Proline Prosonic Flow P 500:
Table of Contents

Advertisement

Proline Prosonic Flow P 500 HART
6.4

Operation

For detailed information on the operating options, see the Operating Instructions.
6.5

Maintenance

For detailed information on maintenance, see the Operating Instructions.
Alternative monitoring measures must be taken to ensure process safety during
configuration, proof-testing and maintenance work on the device.
6.6

Repair

Repair means restoring functional integrity by replacing defective components.
Components of the same type must be used for this purpose. It is recommended to
document the repair. This includes specifying the device serial number, the repair date,
the type of repair and the individual who performed the repair.
For detailed information on returns, see the Operating Instructions.
6.6.1
Replacing device components
The following components may be replaced by the customer' s technical staff if genuine spare
parts are used and the appropriate installation instructions are followed:
• Sensor
• Transmitter without a sensor
• Display module
• Power unit
• Main electronics module
• I/O-Module
• Terminals
• Connection compartment cover
• Electronics compartment cover
• Seal sets for electronics compartment cover
• Securing clamps for electronics compartment cover
• Cable glands
Installation Instructions: see the Download Area at www.endress.com.
The replaced component must be sent to Endress+Hauser for the purpose of fault analysis if
the device has been operated in a protective system and a device error cannot be ruled out. In
this case, always enclose the "Declaration of Hazardous Material and Decontamination" with
the note "Used as SIL device in protection system" when returning the defective device. Please
also refer to the "Return" section in the Operating Instructions. .
6.7

Modification

Modifications are changes to devices with SIL capability already delivered or installed.
Modifications to devices with SIL capability are usually performed in the Endress+Hauser
manufacturing center.