Endress+Hauser Proline Prosonic Flow P 500 Functional Safety Manual page 13

Ultrasonic time-of-flight flowmeter hart
Hide thumbs Also See for Proline Prosonic Flow P 500:
Table of Contents

Advertisement

Proline Prosonic Flow P 500 HART
4.2.2
Useful lifetime of electric components
The established failure rates of electrical components apply for a useful lifetime of 12 years as
per IEC 61508-2: 2010, section 7.4.9.5, note 3.
The device' s year of manufacture is coded in the first character of the serial number (→ table
below).
Example: serial number L5ABBF02000 → year of manufacture 2016
ASCII character
D
E
F
H
J
4.2.3
Suitability of the measuring device
1.
Carefully select the frequency of the sensor set in accordance with the application' s
expected flow rates.
 The maximum flow rate during operation must not exceed the specified maximum
value for the sensor.
2.
In safety-related applications, it is advisable to select the limit value for monitoring a
minimum flow such that this limit is at least twice the smallest specified flow that can
still be measured, with the actual medium.
 For further information, see the Technical Information
3.
The sound velocity of the medium must be in the 600 to 2 100 m/s range.
4.
The additional measuring uncertainties in the event of an error apply for
Reynolds numbers > 10000. SIL mode is not recommended for
Reynolds numbers < 10000.
Endress+Hauser
Meaning
ASCII character
2010
K
2011
L
2012
M
2013
N
2014
P
Meaning
ASCII character
2015
R
2016
S
2017
T
2018
V
2019
W
Safety function
Meaning
2020
2021
2022
2023
2024
13