Endress+Hauser Proline Prosonic Flow P 500 Functional Safety Manual page 30

Ultrasonic time-of-flight flowmeter hart
Hide thumbs Also See for Proline Prosonic Flow P 500:
Table of Contents

Advertisement

Use in protective systems
2.
Compare current at output 1 with this default value.
Comparing the current values
The current values can be compared using one of the following methods:
• Measure the current of the DUT at the logic subsystem (process control system or safety-
related PLC).
• Measure the current at the DUT using an external, traceably-calibrated ammeter.
Compare the current values.
Connecting the measuring equipment and external testing
• Connecting the measuring equipment in the measuring circuit
• External check of the passive current output
Requirements for the measuring equipment:
• DC current measuring uncertainty ±0.2 %
• DC current resolution10 µA
1
 3
External verification taking the example of a passive current output
1
Automation system with current input (e.. g. PLC)
2
Power supply unit
3
Ammeter
4
Transmitter
1.
Connect the ammeter to the transmitter by looping it in series into the circuit.
2.
Connect the power supply unit.
Evaluation of results - Part 2: Testing of current output 1
The amount of deviation between the measured current and the set point must not exceed the
measured error specified for the safety function. The deviation should not exceed ±1 % /
±300 µA.
Note data relating to measured error→  14.
Connecting the test
1.
Re-activate the locked SIL mode→  19.
2.
Deactivate bypassing of safety function of process control system.
30
2
Proline Prosonic Flow P 500 HART
3
A
4
A0034446
Endress+Hauser