Endress+Hauser Proline Prosonic Flow P 500 Functional Safety Manual page 19

Ultrasonic time-of-flight flowmeter hart
Hide thumbs Also See for Proline Prosonic Flow P 500:
Table of Contents

Advertisement

Proline Prosonic Flow P 500 HART
Overview of the SIL mode
The SIL mode enables the following steps:
1.
Makes sure that the preconditions are met.
 The measuring device checks whether the user has correctly configured a
predefined set of parameters for the safety function.
If the result is positive, the device continues with the activation of the SIL mode.
If the result is negative, the sequence is not permitted or is aborted, and the device
does not continue with the activation of the SIL mode.
2.
Automatically switches a predefined set of parameters to the default values specified by
the manufacturer.
 This parameter set ensures that the flowmeter works in the safety mode.
3.
Guides the user through the preconfigured parameters for checking.
 This ensures that the user actively checks all the important pre-settings.
4.
Activates write protection for all the relevant parameters in the SIL mode.
All this ensures that the parameter settings that are required for the safety function are
configured correctly. (These settings cannot be circumvented either deliberately or by
accident.)
5.2.2
Locking a SIL device
When locking a SIL device, all safety-related parameter settings are shown to the operator
individually and must be confirmed explicitly. Parameter settings not permitted in the locked
SIL mode are reset to their default values where necessary. A SIL locking code is then entered
to lock the device software to ensure that parameters cannot be changed. Non-safety-related
parameters remain unchanged.
Endress+Hauser
Use in protective systems
19