Use in protective systems
This behavior occurs in the case of the following diagnostic messages:
803 Current loop diagnostic message
5.2
Parameter configuration for safety-related applications
5.2.1
Configuring the parameters of the measuring point
The measuring point is calibrated via the operating interfaces. A wizard guides you
systematically through all the submenus and parameters that have to be set for configuring
the measuring device.
For detailed information on the operating options, see the Operating Instructions.
For detailed information on configuring the measuring device, see the Operating
Instructions and Description of Device Parameters
To activate the SIL mode, the device must run through a confirmation sequence. While
running through this sequence, critical parameters are either set automatically by the device
to standard values or transferred to the local display/operating tool to enable verification of
the setting. On completion of parameter configuration, the SIL mode of the device must be
enabled with a SIL locking code.
Availability of the SIL mode function
NOTICE
The SIL confirmation sequence is only visible on the local display and in the operating
tools for devices with the order code for "Additional approval", option LA "SIL".
For this reason, the SIL mode can also only be activated on these measuring devices.
If the LA "SIL" option was ordered for the flowmeter ex works, this option is available when
the measuring device is delivered to the customer. Access is via the operating interfaces of
the measuring device.
If the order option cannot be accessed in the measuring device, the function cannot be
retrofitted during the life cycle of the device. If you have any questions please contact your
Endress+Hauser service or sales organization.
Ways to check function availability in the measuring device:
Using the serial number:
W@M Device viewer
Detailed information concerning the SIL label:
• Permitted device types →  9
• SIL label on the transmitter nameplate →  10
1)
www.endress.com/deviceviewer
18
1)
→ Order code for "Additional approval", option LA "SIL"
Proline Prosonic Flow P 500 HART