Endress+Hauser Proline Prosonic Flow P 500 Functional Safety Manual page 36

Ultrasonic time-of-flight flowmeter hart
Hide thumbs Also See for Proline Prosonic Flow P 500:
Table of Contents

Advertisement

Use in protective systems
Evaluation of results - Part 2: Testing of current output 1
The amount of deviation between the measured current and the set point must not exceed the
measured error specified for the safety function. The deviation should not exceed ±1 % /
±300 µA.
Note data relating to measured error→  14.
Connecting the test
1.
Re-activate the locked SIL mode→  19.
2.
Deactivate bypassing of safety function of process control system.
3.
Document results of proof test in accordance with the safety management guidelines
applicable to the system.
NOTICE
At least 99 % of dangerous, undetected failures are detected using these test sequences
(PTC = 0.99). The influence of systematic errors on the safety function is not fully
covered by the test. Systematic faults can be caused, for example, by medium properties,
operating conditions, build-up or corrosion.
If one of the test criteria from the test sequences described above is not fulfilled, the device
may no longer be used as part of a protective system.
Take measures to reduce systematic errors.
Detailed information on:
• Orientation
• Medium properties
• Operating conditions
Operating Instructions
Current output 1 to n simulation
Navigation
Description
Selection
36

Diagnostics → Simulation → Current output 1 to n simulation
(0354–1 to n)
Use this function to switch simulation of the current output on and
off. The display alternates between the measured value and a
diagnostic message of the "Function check" category (C) while
simulation is in progress.
On
Proline Prosonic Flow P 500 HART
Endress+Hauser