Endress+Hauser Proline Prosonic Flow P 500 Functional Safety Manual page 37

Ultrasonic time-of-flight flowmeter hart
Hide thumbs Also See for Proline Prosonic Flow P 500:
Table of Contents

Advertisement

Proline Prosonic Flow P 500 HART
Additional
information
Current output value
Navigation
Prerequisite
Description
User entry
Additional
information
Endress+Hauser
Description
The desired simulation value is defined in the Value current
output 1 to n parameter.
Selection
• Off
Current simulation is switched off. The device is in normal
measuring mode or another process variable is being simulated.
• On
Current simulation is active.

Diagnostics → Simulation → Current output value (0355)
In the Current output 1 to n simulation parameter, the On option
is selected.
Use this function to enter a current value for the simulation. In this
way, users can verify the correct adjustment of the current output
and the correct function of downstream switching units.
• 1. Default value: Select 4.0 mA.
• 2. Default value: Select 20.0 mA.
or
3.59 to 22.5 mA
Dependency
The input range is dependent on the option selected in the Current
span parameter.
Use in protective systems
37