If the SIL confirmation sequence is aborted before the "End of sequence" message is
displayed, the SIL device is not locked. The safety-oriented parameter settings have been
made but the SIL device has not been locked.
Perform SIL device locking again.
5.2.3
Unlocking a SIL device
A device in the locked SIL mode is protected against unauthorized operation by means of a SIL
locking code and, where applicable, by means of a user-specific release code and a hardware
write protection switch. The device must be unlocked in order to change parameters, for
proof-tests as well as to reset self-holding diagnostic messages.
NOTICE
Unlocking the device deactivates diagnostic functions, and the device may not be able to
carry out its safety function in the unlocked SIL mode.
Therefore, independent measures must be taken to ensure that there is no risk of danger
while the SIL device is unlocked.
Unlocking procedure:
1.
Check the write protection switch (WP) in the connection compartment.
2.
Set this switch to the OFF position where necessary.
 Hardware write protection disabled.
3.
Enter the user-specific release code if necessary.
4.
In the Setup menu → Advanced setup submenu, select the Deactivate SIL wizard.
5.
Select Reset write protection parameter.
6.
Enter the SIL locking code 7452.
 If the SIL locking code has been entered correctly, the message "End of sequence"
appears on the display.
7.
Press the  key to confirm.
The SIL mode is now deactivated.