Please check and test emergency stop circuits after wiring. (Installer is responsible for
the correct wiring.)
Never touch any of the input or output power lines directly or allow any input of output
power lines to come in contact with the inverter case.
Do not perform a dielectric voltage withstand test (megger) on the inverter this will result
in inverter damage to the semiconductor components.
Caution
The line voltage applied must comply with the inverter's specified input voltage.
Connect braking resistor and braking unit to the designated terminals.
Do not connect a braking resistor directly to the DC terminals P (+) and N (-), otherwise
fire may result.
Use wire gauge recommendations and torque specifications.
Never connect input power to the inverter output terminals U/T1, V/T2, W/T3.
Do not connect a contactor or switch in series with the inverter and the motor.
Do not connect a power factor correction capacitor or surge suppressor to the inverter
output.
Ensure the interference generated by the inverter and motor does not affect peripheral
devices.
1.3
Before Operation
Warning
Make sure the inverter capacity matches the parameters 13-00.
Reduce the carrier frequency (parameter 11-01) If the cable from the inverter to the
motor is greater than 80 ft (25m). A high-frequency current can be generated by stray
capacitance between the cables and result in an overcurrent trip of the inverter, an
increase in leakage current, or an inaccurate current readout.
Be sure to install all covers before turning on power. Do not remove any of the covers
while power to the inverter is on, otherwise electric shock may occur.
Do not operate switches with wet hands, otherwise electric shock may result.
Do not touch inverter terminals when energized even if inverter has stopped, otherwise
electric shock may result.
1.4
Parameters Setting
Caution
Do not connect a load to the motor while performing a rotational auto-tune.
Make sure the motor can freely run and there is sufficient space around the motor
when performing a rotational auto-tune.
1.5
Operation
Warning
Be sure to install all covers before turning on power. Do not remove any of the covers
while power to the inverter is on, otherwise electric shock may occur.
Do not connect or disconnect the motor during operation. This will cause the inverter
to trip and may cause damage to the inverter.
Operations may start suddenly if an alarm or fault is reset with a run command
active. Confirm that no run command is active upon resetting the alarm or fault,
otherwise accidents may occur.
Do not operate switches with wet hands, otherwise electric shock may result.
It provides an independent external hardware emergency switch, which emergently shuts
down the inverter output in the case of danger.
If automatic restart after power recovery (parameter 07-00) is enabled, the inverter will
2