Auto-Tuning Error - TECO F510 Series Quick Setting Manual

Hide thumbs Also See for F510 Series:
Table of Contents

Advertisement

Available languages

Available languages

LED display
Reconnect and if the
EEPROM
warning signal appears
Archiving Error
again, replace the circuit
board.
Contact TECO for more
information.
Control Board
Error
Replace the control
board.
Wrong Running
Cancel the run command
Direction Error
for another direction on
the terminal of control
board.
PTC Signal
Check if MT terminal and
Loss
GND terminal are
connected.
Parameters
Locked
Correct password input at
parameter 13-07
Password
Password input at the
Setting Error
second time is the same
as that at the first time
when the password lock
function enables.
Operator
Check if the inverter is
Reading Error
normally connected to the
operator.
RDE*
Operator
Check the inverter's
Writing Error
firmware version/ control
mode/ models
WRE*
Operator
Check if the inverter is
Verifying Error
normally connected to
the operator.
VRYE*
Repeat Run
Command
Cancel the run command
in reverse direction from
the external terminal.
Operator Read
Set parameter 16-08 to 1
Prohibit
(Allow to read inverter
parameters and save it
RDP*
to the operator).
External
Remove & shutdown the
Emergency
run command of external
Stop
emergency stop and
reset it to multi-function
digital input.
Zero Speed
Stop Warning
Set up the frequency
command.
Possible solutions
LED display
Overload of Air
Compressor
PID feedback
signal loss
* RDE、WRE、VRYE、RDP warning signals are
only displayed in LCD keypad.

4.4 Auto-tuning Error

When a fault occurs during auto-tuning of a
standard AC motor, the display will show the
"AtErr" fault and the motor stops. The fault
information is displayed in parameter 17-11.
Note: The fault contact output does not
energize with an auto-tuning fault.
Refer to Table 4.3 for fault information
during tuning, cause and corrective
action.
Table 4.3 Auto-tuning fault and corrective
actions
Error
01
Motor data input
error.
02
Motor lead to
lead resistance
R1 tuning error.
03
Motor leakage
inductance tuning
error.
04
Motor rotor
resistance R2
tuning error.
05
Motor mutual
inductance Lm
tuning error.
07
Deadtime
compensation
detection error
08
Motor
acceleration error
(Rotational type
auto-tuning only).
56
Possible solutions
Check if the compressor
load used is higher than
the standard one.
Check 23-19 setting.
Make sure correct
installation and PID
feedback signal.
Corrective action
Check the motor
tuning data (17-00 to
17-09).
Check inverter
capacity
Check the motor
tuning data (17-00 to
17-09).
Check motor
connection.
Disconnect motor
load.
Check inverter current
detection circuit and
DCCTs.
Check motor
installation.
Increase acceleration
time (00-14).
Disconnect motor
load.