Pm Motor Auto-Tuning Error - TECO F510 Series Quick Setting Manual

Hide thumbs Also See for F510 Series:
Table of Contents

Advertisement

Available languages

Available languages

Error
Check the motor
09
tuning data (17-00 to
Other auto-tuning
17-09).
errors
Check motor
connection.

4.5 PM Motor Auto-tuning Error

When a fault occurs during auto-tuning of a
PM motor, the display will show the "IPErr"
fault and the motor stops. The fault
information is displayed in parameter 22-22.
Note: The fault contact output does not
energize with an auto-tuning fault.
Refer to Table 4.4, for fault information
during tuning, cause and corrective
action.
Table 4.4 Auto-tuning fault and corrective
actions for PM motor
Error
01
Magnetic pole
alignment tuning
failure (static).
02~04
Reserved
05
Circuit tuning time
out.
06
Reserved
07
Other motor tuning
errors.
08
Reserved
09
Current out of
range during circuit
tuning.
10
Reserved
11
Parameter tuning
and detecting time
out.
Corrective action
Corrective action
Check the motor
tuning data (22-02).
Check inverter
capacity
Check for active
protection functions
preventing auto-
tuning.
Check the motor
tuning data (22-02).
Check motor
connection.
Check the motor
tuning data (22-02).
Check inverter
capacity
Check if the setting
value of parameter 22-
11 is too low, but its
value cannot exceed
100% of the inverter.
Check motor
connection.
57