Summary of Contents for TECO F510 Series

  • Page 2: Chapter 1 Safety Precautions

    Chapter 1 Safety Precautions 1.1 Before Supplying Power to the Inverter Warning  The main circuit must be correctly wired. For single phase supply use input terminals (R/L1, T/L3) and for three phase supply use input terminals (R/L1, S/L2, T/L3). Terminals U/T1, V/T2, W/T3 must only be used to connect the motor.
  • Page 3: Before Operation

     Never connect input power to the inverter output terminals U/T1, V/T2, W/T3.  Do not connect a contactor or switch in series with the inverter and the motor.  Do not connect a power factor correction capacitor or surge suppressor to the inverter output.
  • Page 4: Maintenance, Inspection And Replacement

    Do not use the inverter braking function for mechanical holding, otherwise injury may  result.  Do not check signals on circuit boards while the inverter is running. 1.6 Maintenance, Inspection and Replacement Warning  Wait a minimum of 5 minutes after power has been turned OFF before starting an inspection.
  • Page 5: System Diagram

    Chapter 2 Environment and Installation 2.1 System Diagram ~ ~ ~ Power supply: Power Supply  Make sure the correct voltage is applied to avoid damaging the inverter. Molded-case circuit breaker (MCCB) or fused disconnect: Molded  A molded-case circuit breaker or fused disconnect must be installed Circuit between the AC source and the inverter that conforms to the rated Breaker...
  • Page 6: General Wiring Diagram

    2.2 General Wiring Diagram The following is the standard wiring diagram for the F510 inverter (◎ indicates main circuit terminals and ○ indicates control circuit terminals ). Locations and symbols of the wiring terminal block might be different due to different models of F510. The description of control circuit terminals and main circuit terminals can be referred to Table 2.1, 2.2 and 2.3...
  • Page 7: Terminal Description

    2.3 Terminal Description Table 2.1 Description of main circuit terminals (IP00/IP20 Type) 200V : 1~30HP 200V : 40~175HP Terminal 400V : 1~40HP 400V : 50~800HP R/L1 S/L2 Input Power Supply T/L3 B1/P  B1/P-:DC power supply  B1/P-B2:external braking resistor ...
  • Page 8 Table 2.3 Description of control circuit terminals Type Terminal Terminal function Signal level/ information 2-wire forward rotation/ stop command (default), multi- function input terminals * 1 2-wire reversal rotation/ stop command (default), multi- Signal Level 24 VDC function input terminals * 1 (opto-isolated) Digital Multi-speed/ position setting command 1 (default), multi-...
  • Page 9 Table 2.3 Description of control circuit terminals (Continued) Type Terminal Terminal function Signal level/ information Relay A contact (multi-function output terminal) Relay B contact (multi-function output terminal) R1A- Rating: Relay contact common terminal, please refer to R1B- 250Vac: 10 mA ~ 1A parameter group 03 in this manual for more functional 30Vdc: 10 mA ~ 1A Relay...
  • Page 10: Cooling Fan Supply Voltage Selection (400V Class)

    2.4 Cooling Fan Supply Voltage Selection (400V class) The inverter input voltage range of the F510 400V class models ranges from 380 to 460Vac. In these models the cooling fan is directly powered from the power supply. Inverter models F510-4150/ 4175/ 4215/ 4250/ 4300/ 4375/ 4425/ 4535/ 4670/ 4800-H3 requires the user to select the correct jumper position based on the inverter input voltage ("400V"...
  • Page 11: Chapter 3 Programming Functions

    Chapter 3 Programming Functions Parameter Name Group Group 00 Basic Parameters Group 01 V/F Control Parameters Group 02 IM Motor Parameters Group 03 External Digital Input and Output Parameters Group 04 External Analog Input and Output Parameters Group 05 Multi-Speed Parameters Group 06 Automatic Program Operation Parameters Group 07...
  • Page 12 Group 00 Basic Parameters Group 00 Basic Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name 0: V/F UP/ DOWN 1: Reserved Control Communication 2: SLV 00-00 Mode Control (RS- Selection 3~4: Reserved 485) 5: PM SLV 4: Reserved Motor’s...
  • Page 13 Group 00 Basic Parameters Group 00 Basic Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Deceleratio 00-34 00-17 0.1~6000.0 n Time 2 Reserved 00-40 00-18 0.00~400.00 6.00 Frequency User 00-41 Parameter 0 00-19 Acceleration 0.1~0600.0 User...
  • Page 14 Group 01 V/F Control Parameters Group 02 IM Motor Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name 200V: Rated 02-05 0.01~600.00 Middle Power 0.0~255.0 01-05 Output Rated 50.0/ 400V: Voltage 2 02-06 4.8~400.0 Frequency 60.0 0.0~510.0...
  • Page 15 Group 03 External Digital Input and Group 03 External Digital Input and Output Parameters Output Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name 5: Multi-Speed 22~23: Multi- Setting Reserved function Command 4 24: PLC Input 03-02 Terminal 6: Forward Jog...
  • Page 16 Group 03 External Digital Input and Group 03 External Digital Input and Output Parameters Output Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name 54: Switch Reserved PID1 and PID2 0xxxb: 55: RTC Time Reserved Enable 1xxxb:...
  • Page 17 Group 03 External Digital Input and Group 03 External Digital Input and Output Parameters Output Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Reference 59: Over Missing Temperature Note6 Detection 27: Timing Function Frequency Output 03-13...
  • Page 18 Group 03 External Digital Input and Group 03 External Digital Input and Output Parameters Output Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name 1: PWM (Pulse Detection Width Level 4 Modulation) Frequency Pulse Input 03-51 Detection 0.0~400.0...
  • Page 19 Group 04 External Analog Input and Group 04 External Analog Input and Output Parameters Output Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name 8: Frequency 18: d-axis Lower Limit Voltage 9: Jump 19~20: Frequency 4 Reserved 10: Added to...
  • Page 20 Group 05 Multi-Speed Function Group Group 05 Multi-Speed Function Group Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Frequency Frequency Setting of Setting of 05-01 0.00~400.00 5.00 05-16 0.00~400.00 5.00 Speed- Speed- Stage 0 Stage 15 Frequency Acceleration...
  • Page 21 Group 05 Multi-Speed Function Group Group 05 Multi-Speed Function Group Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Deceleration of Multi Time Setting Speed 15 05-32 0.1~6000.0 10.0 of Multi Speed 7 Acceleration Time Setting 05-33 0.1~6000.0 10.0...
  • Page 22 Group 06 Automatic Program Group 06 Automatic Program Operation Parameters Operation Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name the last stage. Operation - Restart speed Stage 14 is based on the Frequency previous Setting of 06-15...
  • Page 23 Group 06 Automatic Program Group 06 Automatic Program Operation Parameters Operation Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Setting of Direction 0: Stop 1: Operation - Selection of 06-44 Forward 2: Stage 13 Operation - Reverse Stage 12...
  • Page 24 Group 07: Start /Stop Parameters Group 07: Start /Stop Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Braking SLV Speed 0: Enable Time at 07-26 Search 1: Disable Stop Function 0: Deceleration Start 0: Speed to Stop Selection...
  • Page 25 Group 07: Start /Stop Parameters Group 08 Protection Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Time of PM Stall Speed Prevention 08-03 30~200 Search Level in Operation STP2 0:STP2 Enable 07-45 Function 08-04 Reserved Note6...
  • Page 26 Group 08 Protection Parameters Group 08 Protection Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Detection 1: Start to Limit of Stall Detect when Prevention 08-21 1~100 Reaching the in Acc over Set Frequency. Base Speed 2: Start to Stall...
  • Page 27 Group 08 Protection Parameters Group 08 Protection Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Level 2: Motor 1 Maximum 0: Disable Frequency (01- 08-45 1: Warning Disconnectio Note3 n Detection 2: Fault 0: Forward Over- Fire Mode...
  • Page 28 Group 09: Communication Parameters Group 10: PID Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name to Stop Based xx0xb: PID on Deceleration Positive Time 2 when Characteristic Communication xx1xb: PID Fault Occurs. Negative 3: Keep Characteristic Operating...
  • Page 29 Group 10: PID Parameters Group 10: PID Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Waking up 13: HP Delay Time 14: m/s 10-20 of PID 0.0~255.5 15: MPM Waking up 16: CMM 10-21 Reserved 17: W...
  • Page 30 Group 11: Auxiliary Parameters Group 11: Auxiliary Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name 0: Carrier Saving Output Voltage Carrier Frequency Inverter Upper Limit 11-01 Tuning Frequency 11-21 of Energy 0~100 1: 1~16: Saving 1~16KHz Tuning...
  • Page 31 Group 11: Auxiliary Parameters Group 11: Auxiliary Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Deceleration 200V: 0: Stop Key is Start Voltage 200V: 200~400V Disabled when 11-38 Note2 of OV 400V: 400~800V 400V: the Operation Prevention...
  • Page 32 Group 11: Auxiliary Parameters Group 12: Monitoring Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Soft PWM Decimal Place Function 2 (x.xx) Gain of 0: xxxxx (no 11-69 Preventing 0.00~200.00 5.00 unit) Note2 Feedback Oscillation 3 1: xxxPb...
  • Page 33 Group 12: Monitoring Parameters Group 12: Monitoring Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Output Display the current Al1 input (0V corresponds Frequency output 12-13 to 0%, 10V of Current frequency of corresponds to Fault current fault...
  • Page 34 Group 12: Monitoring Parameters Group 12: Monitoring Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Display the Display the Heatsink heatsink DIO Status DI/DO status of 12-41 Temperatur temperature of 12-50 of Current current fault IGBT Fault...
  • Page 35 Group 12: Monitoring Parameters Group 13 Maintenance Function Group Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name message 0: Disable to Clear 12-65 Clear Cumulative Reserved Cumulative Operation 12-66 13-02 Operation Hours Accumulativ Hours 1: Clear 12-67 e Energy...
  • Page 36 Group 13 Maintenance Function Group Group 13 Maintenance Function Group Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name 8: PLC Fault Two Fault Initialization Message Message 9: 2 Wire Previous Display Previous 13-23 Initialization Three Fault Three Fault Note2...
  • Page 37 Group 13 Maintenance Function Group Group 14: PLC Setting Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Message T5 Set Previous Value 2 14-09 0~9999 Display Previous Twenty Three (Mode 7) 13-43 Twenty Three Note2 Fault Fault Message...
  • Page 38 Group 14: PLC Setting Parameters Group 15: PLC Monitoring Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Value 1 T7 Current 15-12 0~9999 Value 1 MD1 Set 14-37 0~65534 Value 2 T7 Current 15-13 Value 2 0~9999...
  • Page 39 Group 16: LCD Function Parameters Group 16: LCD Function Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name displays in the display of X.XXX second line. at 100%. (default is output 0: No Unit frequency) 1: FPM 5~82...
  • Page 40 Group 16: LCD Function Parameters Group 16: LCD Function Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name RTC Time 0: Hide 16-10 Display 16:Off, 1: Display Setting 17:Off+P1 18:Off+P2, RTC Date 12.01.01 ~ 12.01.0 16-11 19:Off+P1+P2...
  • Page 41 Group 17: IM Motor Automatic Tuning Group 17: IM Motor Automatic Tuning Parameters Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name 0: Rotational 7: DT Error Auto-tuning 8: Motor 1: Static Auto- Acceleration tuning Error 2: Stator...
  • Page 42 Group 20 Speed Control Parameters* Group 20 Speed Control Parameters* Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name 20-00 ASR Gain 1 0.00~250.00 3.00 Frequency 1 SLV: ASR Gain 0.500 20-16 Change 0.0~400.0 20-01 Integral 0.001~10.000 PMSLV...
  • Page 43 Group 22: PM Motor Parameters- Group 22: PM Motor Parameters- only available when PM Control Mode only available when PM Control Mode is selected is selected Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Rated Motor 5: Circuit...
  • Page 44 Group 23 Pump & HVAC Function Group 23 Pump & HVAC Function Parameters Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name 0: Disable of High Pressure 1: Pump Function 23-20=0 : 0.00 23-00 2: HVAC Selection Minimum...
  • Page 45 Group 23 Pump & HVAC Function Group 23 Pump & HVAC Function Parameters Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Detection Accumulating) Time of 1: Enable Multiple Electricity 23-30 Pumps in 0.0 ~ 30.0 23-43 Price per 0.000 ~ 5.000...
  • Page 46 Group 23 Pump & HVAC Function Group 23 Pump & HVAC Function Parameters Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name PID Error Error 23-56 Level of 0 ~ 30 0: Disable Low Suction 1: High Flow Current High...
  • Page 47 Group 24 Pump Control Function Group 24 Pump Control Function Parameters Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Cycling. Note1 Bias of 8: Cycle Modes Pump of Inverter Pump Switch 1 to 3 Relay: Pump 0: 1 to 8 pump First on and First...
  • Page 48: Troubleshooting And Fault Diagnostics

    Chapter 4 LED display Possible solutions Add reactor to power source  Troubleshooting and Fault Diagnostics over current Set the longer acceleration  4.1 General time Inverter fault detection and early warning / Replace motor.  self-diagnosis function. When the inverter Check the motor wiring.
  • Page 49 LED display Possible solutions LED display Possible solutions Check and reduce motor  load, check and operation External fault duty cycle. (S5) Check V/f curve.  Inverter Replace inverter with larger  overload rating. Check and reduce motor  External fault Multi-function input function ...
  • Page 50: Warning / Self-Diagnosis Detection Function

    LED display Possible solutions When the inverter detected a programming Communication Replace the control board  error (for example two parameters contradict Error each other of are set to an invalid setting), the keypad displays a self-diagnostics code. CF01 Note: The fault contact output does not Operator energize on a self-diagnostics error.
  • Page 51 LED display Possible solutions LED display Possible solutions error (flash) Check under torque  under torque detection parameters (08- detection 19 / 08-20). Check load / application.  over current Check load and duty cycle protection  operation. level B (flash) External baseblock...
  • Page 52 LED display Possible solutions LED display Possible solutions HFPB Check feedback signal is  High flow error correct. Check if feedback value  SE01 is lower than limit of Range setting maximum flow. error Check parameter setting.  L0PB Check feedback signal is ...
  • Page 53: Auto-Tuning Error

    Check if the compressor  warning signal appears Archiving Error load used is higher than again, replace the circuit the standard one. board. Contact TECO for more  information. PID feedback Control Board Check 23-19 setting.  signal loss Error Make sure correct ...
  • Page 54: Pm Motor Auto-Tuning Error

    Error Corrective action Increase acceleration  Motor time (00-14). acceleration error Disconnect motor  (Rotational type load. auto-tuning only). Check the motor  tuning data (17-00 to Other auto-tuning 17-09). errors Check motor  connection. 4.5 PM Motor Auto-tuning Error When a fault occurs during auto-tuning of a PM motor, the display will show the “IPErr”...
  • Page 55 第 1 章 安全注意事項 1.1 送電前 警告  主回路端子必須正確配線,單相(R/L1、S/L2)/三相(R/L1、S/L2、T/L3)為電源輸入端 子,絕對不可以與 U/T1、V/T2、W/T3 混用;混用時,送電將造成變頻器的損壞。 注意  所選用之電源電壓必須與變頻器之輸入電壓規格相同。  搬運變頻器時,請勿直接提取前蓋,應由變頻器本體搬運,以防止前蓋脫落,避免變頻 器掉落造成人員受傷或變頻器損壞。  請將變頻器安裝於金屬類等不燃物材料之上,請勿安裝於易燃性材料上或附近,以防止 發生火災。  若多台變頻器同放在一個控制盤內,請外加散熱風扇,使盤內溫度低於 40℃ 以下,以 防過熱或火災等發生。  請於關閉電源後,再拆卸或裝入操作器,並請按圖操作固定操作器,以免接觸不良造成 操作器故障或不顯示。 警告  本產品系通過 IEC 61800-3 限制區域使用等級。在某些環境下使用本產品時,可能造成 電磁干擾,故在使用前請先進行適當的測試,同時請務必做好接地工程。  馬達過溫度保護功能,請依照控制迴路端子說明進行配線,並參考參數群組 08 之說 明。...
  • Page 56 1.4 參數設定 注意  進行旋轉型自動調校時,請勿將馬達連接到負載(機械設備)上。  進行旋轉型自動調校時,馬達將進行旋轉,確認馬達週遭空間,避免造成危險。 1.5 運轉 警告  請確認前外蓋安裝完成後,再打開電源。  運轉中不可將馬達機組投入或切離,否則會造成變頻器過電流跳脫,嚴重時會造成變頻 器主回路損壞。  進行復歸機能時,請勿靠近機器,故障清除後,機器會再啟動。  勿於雙手潮濕時操作機器。  提供一個數位輸入的緊急停止開關,此開關使用在該機能參數被設置時啟用(請參考 08- 30 設定) 。  提供一個獨立外部硬體緊急開關,當遇危險時可緊急關斷變頻器輸出。  復歸警告前請確認運轉命令為關閉的。  若選擇復電後自動重新啟動(07-00),變頻器將在電源回復後自動啟動。  自動調校執行前,請確保週邊系統,機械設備狀態,確保人員安全。  無論變頻器處於運轉或停止狀態,避免觸碰相關端子,以防發生危險。  電源切斷後,風扇可能會繼續旋轉一段時間。 注意  散熱座、煞車電阻等發熱元件請勿觸摸。 ...
  • Page 57 第 2 章 周圍環境及安裝 2.1 系統圖 ■ 電源 電源 ‧ 請確認電壓等級是否正確,以免變頻器損壞。 ■ 無熔絲開關 (NFB) 及漏電斷路器 無熔絲開關 NFB ‧ 請參考使用說明書,選用適當額定電流之 NFB。 (及漏電斷路器) ‧ 請勿使用 NFB 作為變頻器之運轉/停止控制。 ‧ 若加裝漏電斷路器以作漏電故障保護時,請選用 感度電流 200mA 以上,動作時間 0.1 秒以上(V- 電磁接觸器 TYPE),以防止高頻誤動作。 ■ 電磁接觸器 ‧ 一般使用時,可以不加電磁接觸器,但要作外部 AC 電抗器 順序控制或停電後自動再起動等功能時,需加裝...
  • Page 58 2.2 標準配線圖 以下為 F510 變頻器標準配線圖(◎表示主回路端子, ○ 表示控制回路端子),F510 依型號不同,配線端子台的位置及符號會稍有差異。主回路端子及控制回路端子說明 請參考表 2.1、2.2、2.3。...
  • Page 59 2.3 端子機能說明 表 2.1 標準型(IP00/IP20)主回路端子 200V : 1~30HP 200V : 40~175HP 端子標示 400V : 1~40HP 400V : 50~800HP R/L1 S/L2 主回路電源輸入 T/L3 B1/P  B1/P-:直流電源輸入  B1/P-B2:外接煞車電阻   -:直流電源輸入或接   煞車檢出模組 U/T1 V/T2 變頻器輸出 W/T3 接地端子 (第三種接地) 表 2.2 防水型(IP55)主回路端子 400V 機種...
  • Page 60 表 2.3 控制回路端子 種類 端子 端子功能 訊號位準 二線式正轉/停止(預設),多機能輸入端子*1 二線式反轉/停止 (預設), 多機能輸入端子*1 24 VDC, 8 mA 光耦合隔 多段速/位置設定指令 1 (預設), 多機能輸入端子*1 數位 離(最大電壓 30 Vdc, 輸入 多段速/位置設定指令 2 (預設), 多機能輸入端子*1 輸入訊號 阻抗 4.22kΩ) 多段速/位置設定指令 3 (預設), 多機能輸入端子*1 故障復歸 (預設), 多機能輸入端子*1 數位訊號 SOURCE 共同點 (SW3 切至 SOURCE 位 ±15%, 置) 最大輸出電流...
  • Page 61 種類 端子 端子功能 訊號位準 S (+) RS-485 RS485/MODBUS 差動輸出入 S (-) 埠 大地接地 E (G) ---- 接地 屏蔽連接端子 *1:多機能數位輸入功能/ 多機能類比輸入功能/ 多機能類比輸出功能,請參閱使用說明書 注意 ‧ 端子 10V 輸出電流最大容量為 20mA。 ‧ 多機能類比輸出 AO1,AO2 為接電錶專用之類比輸出,請勿用作回授控制等之類比輸出信號。 ‧ 控制板 24V 與 10V 電源僅供內部控制使用,請勿外接至其他裝置供電。 2.4 電源電壓選擇基板之設定 (400V 級) F510 400V 級機種,可適用在...
  • Page 62 第 3 章 軟體索引 參數群組 名 稱 群組 00 基本功能群組 群組 01 V/F 控制功能群組 群組 02 IM 馬達參數群組 群組 03 外部端子數位輸入輸出功能群組 群組 04 外部端子類比輸入輸出功能群組 群組 05 多段速功能群組 群組 06 自動運轉功能群組 群組 07 運轉停止功能群組 群組 08 保護功能群組 群組 09 通訊功能群組 群組 10 PID 功能群組...
  • Page 63 群組 00 基本功能群組 群組 00 基本功能群組 出廠 出廠 代碼 參數名稱 範圍 屬性 代碼 參數名稱 範圍 屬性 設定 設定 0: V/F 0:PID 休眠限制 1:保留 PID 頻率下限 頻率下限 00-11 Note1 2: SLV 選擇 1:PID 休眠限制 00-00 馬達控制模式 3:保留 4:保留 00-12 頻率上限 0.1~109.0 100.0 5: PM SLV 00-13 頻率下限...
  • Page 64 群組 00 基本功能群組 群組 02 IM 馬達參數群組 出廠 出廠 代碼 參數名稱 範圍 屬性 代碼 參數名稱 範圍 屬性 設定 設定 00-46 使用者參數 5 02-00 無載電流 0.01~600.00 00-47 使用者參數 6 25%~200%變頻 02-01 額定電流 00-48 使用者參數 7 器額定電流 02-02 00-49 使用者參數 8 保留 00-50 使用者參數...
  • Page 65 群組 03 外部端子數位輸入輸出功能群組 群組 03 外部端子數位輸入輸出功能群組 出廠 出廠 代碼 參數名稱 範圍 屬性 代碼 參數名稱 範圍 屬性 設定 設定 9: DOWN 減頻率 45: 保留 指令 46: 保留 多功能端子 10: 加減速設定指 03-04 47: 火災模式(強 S5 功能設定 令 1 制運轉模式) 11: 加減速禁止 48: KEB 加速 12: 主副運轉切換...
  • Page 66 群組 03 外部端子數位輸入輸出功能群組 群組 03 外部端子數位輸入輸出功能群組 出廠 出廠 代碼 參數名稱 範圍 屬性 代碼 參數名稱 範圍 屬性 設定 設定 (03-13±03-14) R2C)輸出 51: 頻率檢出 4 Note2 4: 頻率檢出 1 (≧ 52: 頻率檢出 5 03-13+03-14) Note2 5: 頻率檢出 2 (< 53: 頻率檢出 6 03-13+03-14) Note2 6: 自動再啟動...
  • Page 67 群組 03 外部端子數位輸入輸出功能群組 群組 04 外部端子類比輸入輸出功能群組 出廠 出廠 代碼 參數名稱 範圍 屬性 代碼 參數名稱 範圍 屬性 設定 設定 計時器 OFF 4: 加減速縮短係 03-38 0.0~6000.0 延遲 (DI/DO) 數 5: 直流剎車電流 範圍和定義和 繼電器(R3A- 03-11, 03-12 相 03-39 6: 過轉矩偵測準 R3C)輸出 同 位 up/down 頻率...
  • Page 68 群組 04 外部端子類比輸入輸出功能群組 群組 05 多段速功能群組 出廠 出廠 代碼 參數名稱 範圍 屬性 代碼 參數名稱 範圍 屬性 設定 設定 28: 通訊控制 *6 第 12 段速頻 05-13 0.00~400.00 5.00 *7 04-12 AO1 增益值 率設定 0.0~1000.0 100.0 *1 第 13 段速頻 04-13 AO1 偏壓值 -100.0~100.0 05-14 0.00~400.00...
  • Page 69 群組 05 多段速功能群組 群組 06 自動運轉功能群組 出廠 出廠 代碼 參數名稱 範圍 屬性 代碼 參數名稱 範圍 屬性 設定 設定 多段速 11 加 第一段速起開始 05-39 0.1~6000.0 10.0 速時間設定 運轉 多段速 11 減 第 1 段運轉頻 05-40 0.1~6000.0 10.0 06-01 0.00~400.00 5.00 *1 速時間設定...
  • Page 70 群組 06 自動運轉功能群組 群組 07 運轉停止功能群組 出廠 出廠 代碼 參數名稱 範圍 屬性 代碼 參數名稱 範圍 屬性 設定 設定 0:瞬停再啟動無 時間設定 第 11 段運轉 效 瞬停再啟動選 06-27 0.0~6000.0 07-00 1:瞬停再啟動有 擇 時間設定 第 12 段運轉 效 06-28 0.0~6000.0 時間設定 自動復歸再啟 07-01 0~7200 第...
  • Page 71 群組 07 運轉停止功能群組 群組 08 保護功能群組 出廠 出廠 代碼 參數名稱 範圍 屬性 代碼 參數名稱 範圍 屬性 設定 設定 式選擇 加速失速防止 08-01 20~200 SLV 故障後啟 0: 速度尋找啟動 準位 07-27 200V: 330~410 1: 正常啟動 減速失速防止 動方式選擇 08-02 400V: 660~820 準位 0: 速度尋找啟動 遮斷後啟動方...
  • Page 72 群組 08 保護功能群組 群組 08 保護功能群組 出廠 出廠 代碼 參數名稱 範圍 屬性 代碼 參數名稱 範圍 屬性 設定 設定 0: 低轉矩偵測無 2: 故障 效 08-46 溫度到達準位 0~254°C Note6 低轉矩檢測選 1: 到達設定頻率 08-17 08-47 溫度復歸準位 0~254°C Note6 擇 後開始偵測 0: 禁能 08-48 火災模式選擇...
  • Page 73 群組 09 通訊功能群組 群組 10 PID 功能群組 出廠 出廠 代碼 參數名稱 範圍 屬性 代碼 參數名稱 範圍 屬性 設定 設定 4: 19200 xxx1b: PID 有效 5: 38400 xx0xb: PID 正特 0: 1 停止位元 性 09-03 停止位元選擇 1: 2 停止位元 xx1xb: PID 負特 0: 無奇偶位...
  • Page 74 群組 10 PID 功能群組 群組 10 PID 功能群組 出廠 出廠 代碼 參數名稱 範圍 屬性 代碼 參數名稱 範圍 屬性 設定 設定 1: 有效 10-45 預先給水時間 0~250 Note3 2: 由 DI 設定 預先給水目標 10-46 0~10000 Note3 10-30 PID 目標上限 0.0 ~ 100.0 100.0 準位...
  • Page 75 群組 11 輔助功能群組 群組 11 輔助功能群組 出廠 出廠 代碼 參數名稱 範圍 屬性 代碼 參數名稱 範圍 屬性 設定 設定 11-24 自動省能係數 0.00~655.34 11-49 保留 11-50 11-25 0: 零速直流煞車 保留 11-27 無效 11-51 零速煞車選擇 過壓防止2 頻 1: 零速直流煞車 11-28 1~200 Note4 率增益 有效...
  • Page 76 群組 11 輔助功能群組 群組 12 監視功能群組 出廠 出廠 代碼 參數名稱 範圍 屬性 代碼 參數名稱 範圍 屬性 設定 設定 防止振盪時間 有輸入輸出時之 11-71 0~30000 Note2 常數 3 對應 防止振盪增益 11-72 0.01~300.00 30.00 Note2 切換頻率 1 防止振盪增益 11-73 0.01~300.00 50.00 Note2 切換頻率 2 KVA:代表該參數會隨著不同變頻器的容量大小而不同...
  • Page 77 群組 12 監視功能群組 群組 12 監視功能群組 出廠 出廠 代碼 參數名稱 範圍 屬性 代碼 參數名稱 範圍 屬性 設定 設定 0:VF 2:SLV 5:PM SLV 顯示目前的 AI1 有錯誤時之對應 輸入(0V 對應 1: CRC Error 12-25 AI1 輸入 1: Data length Error 1: Data Function Error 0%, 10V 對應...
  • Page 78 群組 12 監視功能群組 群組 13 維護功能群組 出廠 出廠 代碼 參數名稱 範圍 屬性 代碼 參數名稱 範圍 屬性 設定 設定 13-00 變頻器馬力數 00H~FFH 前一次故障輸 顯示上一次故障 12-57 出電壓 時的輸出電壓 13-01 軟體版本 0.00-9.99 前一次故障直 顯示上一次故障 0:不清除累計工 12-58 流電壓 時的直流電壓 作時間 累計工作時間 13-02 1:清除累計工作 顯示上一次故障 清除功能...
  • Page 79 群組 13 維護功能群組 群組 13 維護功能群組 出廠 出廠 代碼 參數名稱 範圍 屬性 代碼 參數名稱 範圍 屬性 設定 設定 (230/400V) 訊息 障的訊息 13:2 線式初始 前十二次故障 顯示前十二次故 Note 13-32 化(50Hz) 訊息 障的訊息 (230/400V) 前十三次故障 顯示前十三次故 Note 13-33 14:3 線式初始 訊息 障的訊息 化(50Hz) 前十四次故障...
  • Page 80 群組 14 PLC 設定群組 群組 14 PLC 設定群組 出廠 出廠 代碼 參數名稱 範圍 屬性 代碼 參數名稱 範圍 屬性 設定 設定 14-00 T1 設定值 1 0~9999 MD2 設定值 14-40 0~65534 T1 設定值 2 14-01 0~9999 MD2 設定值 (模式 7) 14-41 0~65534 14-02 T2 設定值...
  • Page 81 群組 15 PLC 監控群組 群組 16 LCD 功能群組 出廠 出廠 代碼 參數名稱 範圍 屬性 代碼 參數名稱 範圍 屬性 設定 設定 AS1 計算結 15-24 0~65534 3~39:保留 果 AS2 計算結 40~9999: 15-25 0~65534 果 使用者指定格 AS3 計算結 式.輸入 0XXXX 15-26 0~65534 果 表示...
  • Page 82 群組 16 LCD 功能群組 群組 16 LCD 功能群組 出廠 出廠 代碼 參數名稱 範圍 屬性 代碼 參數名稱 範圍 屬性 設定 設定 1:讀取變頻器參 4: 星期四 5: 星期五 數,存至操作器 16-25 P3 結束日 6: 星期六 2:將操作器參數 7: 星期日 寫入變頻器 16-26 P4 啟始時間 00:00 ~ 23:59 08:00 3:比對變頻器和...
  • Page 83 群組 16 LCD 功能群組 群組 17 IM 馬達自動調校功能群組 出廠 出廠 代碼 參數名稱 範圍 屬性 代碼 參數名稱 範圍 屬性 設定 設定 5: 由計時器 1+2 1: 馬達資料錯誤 履歷 2: 定子電阻調校 選擇 錯誤 xxx0b: RTC 3: 漏感調校錯誤 Run1 正轉 4: 轉子電阻調校 xxx1b: RTC 錯誤...
  • Page 84 群組 20 速度控制功能群組 群組 22 PM 馬達群組 出廠 出廠 代碼 參數名稱 範圍 屬性 代碼 參數名稱 範圍 屬性 設定 設定 ASR 積分時 PM 馬達額定 20-04 0~300 22-00 0.00~600.00 間限制 功率 20-05 22-01 保留 保留 20-06 PM 馬達額定 22-02 0.1~999.9 0:PI 速度控制 電流...
  • Page 85 群組 22 PM 馬達群組 群組 23 泵浦與 HVAC 群組 出廠 出廠 代碼 參數名稱 範圍 屬性 代碼 參數名稱 範圍 屬性 設定 設定 650.00 0: 使 用 停 止 前 的 23-20=1 : 0~100 角度 初始磁極偵測 Note 22-25 23-13 高壓警告時間 0.0 ~ 600.0 10.0 1:方式...
  • Page 86 群組 23 泵浦與 HVAC 群組 群組 23 泵浦與 HVAC 群組 出廠 出廠 代碼 參數名稱 範圍 屬性 代碼 參數名稱 範圍 屬性 設定 設定 3:Pa 誤差準位 23-37 漏水檢測時間 0.0~100.0 57 吸力過低 23-20=0 : 0.01 ~ 23-57 0 ~ 100 電流準位(馬 漏水檢測再啟 23-38 65.00 達額定電流) 動壓力變化量...
  • Page 87 群組 24 1 對 8 泵浦卡相關機能群組 群組 24 1 對 8 泵浦卡相關機能群組 出廠 出廠 代碼 參數名稱 範圍 屬性 代碼 參數名稱 範圍 屬性 設定 設定 0xxxb: Relay 4 0: 1 對 8 泵浦卡 無效 動作無效 1xxxb: Relay 4 1: 變頻泵浦固定 有效 模式,依先開後...
  • Page 88 LED 顯示 改正行動 第 4 章 異常診斷及排除 .移除功率因數校正電容。 4.1 總則 UV 電壓過低 .檢查輸入電路和電源電壓。 變頻器的故障檢測和預警/自我診斷功 .延長加速時間。 能。當變頻器檢測到故障的故障碼顯示在數 位操作器時,故障接點輸出動作,切斷變頻 IPL 輸入欠相 .確認主回路電源接線是否正確。 器輸出,使馬達自由運轉停止(在某些故障 .檢查端子螺絲是否鬆動。 .確認電源電壓採取穩定電壓的對 方面,停機的方法是可以選擇)。 策,或將輸入欠相檢出關閉。 當變頻器檢測到警告/自我診斷,數位 .更換電路板或變頻器。 操作器會顯示警告/自診斷代碼,但接點的 OPL 輸出欠相 故障輸出不動作。一旦發生的警告已被排 .檢查馬達的接線。 .檢查馬達和變頻器的容量。 除,系統會自動恢復到原來的狀態。 4.2 故障檢測功能 .檢查變頻器環境周圍的溫度。 散熱座過熱 .檢查風扇或散熱槽之塵埃和污 故障發生時,參閱表 5.1 查詢可能的原因, 垢。...
  • Page 89 LED 顯示 改正行動 LED 顯示 改正行動 限制值(參數 23-12)。 外部故障 0 .檢查外部故障原因。 .檢測出水槽內是否不足,而出 .復歸通訊位置 0x2501 的 bit 2 LSCFT 水槽內是否正常供水。 低吸力故障 .確認 PID 誤差高於 PID 誤差準位 或者電流低於吸力不足輸出電流 準位。 外部故障(S1) CF00 操作器通訊異 .數位操作器之連接器拔起再插入 常 .更換控制基板 外部故障(S2) CF01 操作器通訊異 外部故障(S3) .數位操作器之連接器拔起再插入 常 2 .更換控制基板...
  • Page 90 置),數位操作器將顯示自診斷代碼,且故 LED 顯示 改正行動 障輸出接點不動作;直到參數已經設置正確 前,變頻器無法執行運轉指令。 當一個警告或自我診斷錯誤發生,請參 考表 4.2,以確定和糾正造成的錯誤。 (閃爍) 外部遮斷 表 4.2 警告/自診斷和糾正措施 LED 顯示 改正行動 (閃爍) (閃爍) 外部遮斷 過電壓 檢查輸入電源之電壓。 (閃爍) (閃爍) 外部遮斷 .檢查輸入電源電壓。 低電壓 .檢查輸入電路。 .檢查主回路 MC。 .檢查 V/F 模式。 馬達過載 .檢查馬達額定電流。 .檢查變頻器環境周圍的溫 散熱座過熱 .檢查負載大小和運轉週期時 度。 .檢查風扇或散熱槽之塵埃和 間。...
  • Page 91 LED 顯示 改正行動 LED 顯示 改正行動 .運轉命令關閉,或執行端子 (閃爍) 復歸動作(03-00 至 03-07 無人保護 為 3),或使用數位操作器 EF5 (閃爍) 上的 RESET 鍵進行復歸。 外部故障(S5) .關閉 USP 信號和重新啟閉 電源。 LFPB .檢查回授訊號是否正確且有 EF6 (閃爍) 低流量錯誤 接上。 外部故障(S6) .確認回授流量是否低於最小 流量限制值。 HFPB .檢查回授訊號是否正確。 高流量錯誤 EF9 (閃爍) .確認回授流量是否低於最大 正反轉錯誤 流量限制值。...
  • Page 92 LED 顯示 改正行動 LED 顯示 改正行動 出標準 ADC 電壓錯誤 PID 回授訊號遺 檢查輸入電壓訊號與控制板 .檢查設立的 23-19 失壓比例 失 上的電壓。 是否正確。 .確保正確安裝及 PID 回授 信號的工作正常。 EEPROM 儲存錯誤 * RDE、WRE、VRYE、RDP 為 LCD 介面才會 1. 重新斷送電,若再次出現 警告,則更換電路板。 顯示的警告訊號。 2. 請連絡東元。 4.4 自動調校錯誤 控制板錯誤 當 自 動 調 校 故 障 發 生 時 , 故 障 顯 示 控制板與程式不符合,請更...
  • Page 93 表 4.4 PM 馬達自動調校故障和糾正措施 錯誤 改正行動 ·檢查自動調校所輸入資料 (22-02)。 靜止磁極對位失 ·檢查變頻器的容量。 敗 ·檢查馬達接線。 02~04 Reserved 檢查是否進入其它保護程 迴路調整逾時 序。 Reserved ·檢查馬達接線。 其他馬達調校錯 ·檢查自動調校輸入資料。 誤 Reserved ·檢查自動調校所輸入資料 (22-02)。 迴路調整時,電 ·檢查變頻器的容量。 流異常 Reserved ·檢查參數(22-11)是否設定 過小但最大不得設定超過變 頻器 100%。 參數調測逾時 ·檢查馬達接線。...
  • Page 94: Appendix-A Instructions For Ul

    Teco recommends crimp terminals made by NICHIFU for the insulation cap. The table below matches drives models with crimp terminals and insulation caps. Orders can be placed with a Teco representative or directly with the Teco sales department.
  • Page 95 Fuse Type Drive Model F510 Manufacturer: Bussmann / FERRAZ SHAWMUT Model Fuse Ampere Rating (A) 400 V Class Three-Phase Drives 4001 Bussmann 10CT 690V 10A 4002 Bussmann 10CT 690V 10A 4003 Bussmann 16CT 690V 16A 4005 Bussmann 16CT 690V 16A 4008 Bussmann 25ET 690V 25A...
  • Page 96 Préface  Le produit est un lecteur conçu pour commander un moteur à induction triphasé. lire attentivement ce manuel pour garantir le bon fonctionnement, la sécurité et pour se familiariser avec les fonctions d'entraînement.  Le lecteur est un appareil électrique / électronique et doit être installé et géré par un personnel qualifié...
  • Page 97: Avant L'opération

    1.2 Câblage Avertissement  Coupez toujours l'alimentation électrique avant de procéder à l'installation d'entraînement et le câblage des terminaux utilisateurs.  Le câblage doit être effectué par un personnel qualifié / électricien certifié. Assurez-vous que le lecteur est correctement mis à la terre. (220V Classe: impédance ...
  • Page 98: Entretien, Inspection Et Remplacement

    pendant que l'alimentation du lecteur est allumé, un choc électrique peut se produire autrement. Ne pas brancher ou débrancher le moteur pendant le fonctionnement. Le variateur  pourrai se déclencher et ainsi endommager le lecteur.  Les opérations peuvent commencer soudainement si une alarme ou un défaut est réarmé...
  • Page 99 產品說明書附件 產品中的有害物質的名稱及含量 有毒有害物質或元素 鉛及其化 汞及其化 鎘及其化 六價鉻化合 部件名稱 多溴聯苯 多溴二苯醚 合物 合物 合物 物 (PBB) (PBDE) (Pb) (Hg) (Cd) (Cr(VI)) 電子元器件 電子部件 電磁接觸器 顯示器 接線端子 電線和電纜 導線 絕緣部件 導電銅柱、風扇、 溫控開關 機械部件 其他 本表格依據 SJ/T 11364 的規定編制。 O: 表示該有毒有害物質在該部件所有均質材料中的含量均在 GB/T 26572 規定的限量要求以下。 X: 表示該有毒有害物質至少在該部件的某一均質材料中的含量超出...