Chapter 1 Safety Precautions 1.1 Before Supplying Power to the Inverter Warning The main circuit must be correctly wired. For single phase supply use input terminals (R/L1, T/L3) and for three phase supply use input terminals (R/L1, S/L2, T/L3). Terminals U/T1, V/T2, W/T3 must only be used to connect the motor.
Never connect input power to the inverter output terminals U/T1, V/T2, W/T3. Do not connect a contactor or switch in series with the inverter and the motor. Do not connect a power factor correction capacitor or surge suppressor to the inverter output.
Do not use the inverter braking function for mechanical holding, otherwise injury may result. Do not check signals on circuit boards while the inverter is running. 1.6 Maintenance, Inspection and Replacement Warning Wait a minimum of 5 minutes after power has been turned OFF before starting an inspection.
Chapter 2 Environment and Installation 2.1 System Diagram ~ ~ ~ Power supply: Power Supply Make sure the correct voltage is applied to avoid damaging the inverter. Molded-case circuit breaker (MCCB) or fused disconnect: Molded A molded-case circuit breaker or fused disconnect must be installed Circuit between the AC source and the inverter that conforms to the rated Breaker...
2.2 General Wiring Diagram The following is the standard wiring diagram for the F510 inverter (◎ indicates main circuit terminals and ○ indicates control circuit terminals ). Locations and symbols of the wiring terminal block might be different due to different models of F510. The description of control circuit terminals and main circuit terminals can be referred to Table 2.1, 2.2 and 2.3...
Page 8
Table 2.3 Description of control circuit terminals Type Terminal Terminal function Signal level/ information 2-wire forward rotation/ stop command (default), multi- function input terminals * 1 2-wire reversal rotation/ stop command (default), multi- Signal Level 24 VDC function input terminals * 1 (opto-isolated) Digital Multi-speed/ position setting command 1 (default), multi-...
Page 9
Table 2.3 Description of control circuit terminals (Continued) Type Terminal Terminal function Signal level/ information Relay A contact (multi-function output terminal) Relay B contact (multi-function output terminal) R1A- Rating: Relay contact common terminal, please refer to R1B- 250Vac: 10 mA ~ 1A parameter group 03 in this manual for more functional 30Vdc: 10 mA ~ 1A Relay...
2.4 Cooling Fan Supply Voltage Selection (400V class) The inverter input voltage range of the F510 400V class models ranges from 380 to 460Vac. In these models the cooling fan is directly powered from the power supply. Inverter models F510-4150/ 4175/ 4215/ 4250/ 4300/ 4375/ 4425/ 4535/ 4670/ 4800-H3 requires the user to select the correct jumper position based on the inverter input voltage ("400V"...
Chapter 3 Programming Functions Parameter Name Group Group 00 Basic Parameters Group 01 V/F Control Parameters Group 02 IM Motor Parameters Group 03 External Digital Input and Output Parameters Group 04 External Analog Input and Output Parameters Group 05 Multi-Speed Parameters Group 06 Automatic Program Operation Parameters Group 07...
Page 12
Group 00 Basic Parameters Group 00 Basic Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name 0: V/F UP/ DOWN 1: Reserved Control Communication 2: SLV 00-00 Mode Control (RS- Selection 3~4: Reserved 485) 5: PM SLV 4: Reserved Motor’s...
Page 13
Group 00 Basic Parameters Group 00 Basic Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Deceleratio 00-34 00-17 0.1~6000.0 n Time 2 Reserved 00-40 00-18 0.00~400.00 6.00 Frequency User 00-41 Parameter 0 00-19 Acceleration 0.1~0600.0 User...
Page 14
Group 01 V/F Control Parameters Group 02 IM Motor Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name 200V: Rated 02-05 0.01~600.00 Middle Power 0.0~255.0 01-05 Output Rated 50.0/ 400V: Voltage 2 02-06 4.8~400.0 Frequency 60.0 0.0~510.0...
Page 15
Group 03 External Digital Input and Group 03 External Digital Input and Output Parameters Output Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name 5: Multi-Speed 22~23: Multi- Setting Reserved function Command 4 24: PLC Input 03-02 Terminal 6: Forward Jog...
Page 16
Group 03 External Digital Input and Group 03 External Digital Input and Output Parameters Output Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name 54: Switch Reserved PID1 and PID2 0xxxb: 55: RTC Time Reserved Enable 1xxxb:...
Page 17
Group 03 External Digital Input and Group 03 External Digital Input and Output Parameters Output Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Reference 59: Over Missing Temperature Note6 Detection 27: Timing Function Frequency Output 03-13...
Page 18
Group 03 External Digital Input and Group 03 External Digital Input and Output Parameters Output Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name 1: PWM (Pulse Detection Width Level 4 Modulation) Frequency Pulse Input 03-51 Detection 0.0~400.0...
Page 19
Group 04 External Analog Input and Group 04 External Analog Input and Output Parameters Output Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name 8: Frequency 18: d-axis Lower Limit Voltage 9: Jump 19~20: Frequency 4 Reserved 10: Added to...
Page 20
Group 05 Multi-Speed Function Group Group 05 Multi-Speed Function Group Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Frequency Frequency Setting of Setting of 05-01 0.00~400.00 5.00 05-16 0.00~400.00 5.00 Speed- Speed- Stage 0 Stage 15 Frequency Acceleration...
Page 21
Group 05 Multi-Speed Function Group Group 05 Multi-Speed Function Group Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Deceleration of Multi Time Setting Speed 15 05-32 0.1~6000.0 10.0 of Multi Speed 7 Acceleration Time Setting 05-33 0.1~6000.0 10.0...
Page 22
Group 06 Automatic Program Group 06 Automatic Program Operation Parameters Operation Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name the last stage. Operation - Restart speed Stage 14 is based on the Frequency previous Setting of 06-15...
Page 23
Group 06 Automatic Program Group 06 Automatic Program Operation Parameters Operation Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Setting of Direction 0: Stop 1: Operation - Selection of 06-44 Forward 2: Stage 13 Operation - Reverse Stage 12...
Page 24
Group 07: Start /Stop Parameters Group 07: Start /Stop Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Braking SLV Speed 0: Enable Time at 07-26 Search 1: Disable Stop Function 0: Deceleration Start 0: Speed to Stop Selection...
Page 25
Group 07: Start /Stop Parameters Group 08 Protection Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Time of PM Stall Speed Prevention 08-03 30~200 Search Level in Operation STP2 0:STP2 Enable 07-45 Function 08-04 Reserved Note6...
Page 26
Group 08 Protection Parameters Group 08 Protection Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Detection 1: Start to Limit of Stall Detect when Prevention 08-21 1~100 Reaching the in Acc over Set Frequency. Base Speed 2: Start to Stall...
Page 27
Group 08 Protection Parameters Group 08 Protection Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Level 2: Motor 1 Maximum 0: Disable Frequency (01- 08-45 1: Warning Disconnectio Note3 n Detection 2: Fault 0: Forward Over- Fire Mode...
Page 28
Group 09: Communication Parameters Group 10: PID Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name to Stop Based xx0xb: PID on Deceleration Positive Time 2 when Characteristic Communication xx1xb: PID Fault Occurs. Negative 3: Keep Characteristic Operating...
Page 29
Group 10: PID Parameters Group 10: PID Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Waking up 13: HP Delay Time 14: m/s 10-20 of PID 0.0~255.5 15: MPM Waking up 16: CMM 10-21 Reserved 17: W...
Page 30
Group 11: Auxiliary Parameters Group 11: Auxiliary Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name 0: Carrier Saving Output Voltage Carrier Frequency Inverter Upper Limit 11-01 Tuning Frequency 11-21 of Energy 0~100 1: 1~16: Saving 1~16KHz Tuning...
Page 31
Group 11: Auxiliary Parameters Group 11: Auxiliary Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Deceleration 200V: 0: Stop Key is Start Voltage 200V: 200~400V Disabled when 11-38 Note2 of OV 400V: 400~800V 400V: the Operation Prevention...
Page 32
Group 11: Auxiliary Parameters Group 12: Monitoring Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Soft PWM Decimal Place Function 2 (x.xx) Gain of 0: xxxxx (no 11-69 Preventing 0.00~200.00 5.00 unit) Note2 Feedback Oscillation 3 1: xxxPb...
Page 33
Group 12: Monitoring Parameters Group 12: Monitoring Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Output Display the current Al1 input (0V corresponds Frequency output 12-13 to 0%, 10V of Current frequency of corresponds to Fault current fault...
Page 34
Group 12: Monitoring Parameters Group 12: Monitoring Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Display the Display the Heatsink heatsink DIO Status DI/DO status of 12-41 Temperatur temperature of 12-50 of Current current fault IGBT Fault...
Page 35
Group 12: Monitoring Parameters Group 13 Maintenance Function Group Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name message 0: Disable to Clear 12-65 Clear Cumulative Reserved Cumulative Operation 12-66 13-02 Operation Hours Accumulativ Hours 1: Clear 12-67 e Energy...
Page 36
Group 13 Maintenance Function Group Group 13 Maintenance Function Group Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name 8: PLC Fault Two Fault Initialization Message Message 9: 2 Wire Previous Display Previous 13-23 Initialization Three Fault Three Fault Note2...
Page 37
Group 13 Maintenance Function Group Group 14: PLC Setting Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Message T5 Set Previous Value 2 14-09 0~9999 Display Previous Twenty Three (Mode 7) 13-43 Twenty Three Note2 Fault Fault Message...
Page 38
Group 14: PLC Setting Parameters Group 15: PLC Monitoring Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Value 1 T7 Current 15-12 0~9999 Value 1 MD1 Set 14-37 0~65534 Value 2 T7 Current 15-13 Value 2 0~9999...
Page 39
Group 16: LCD Function Parameters Group 16: LCD Function Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name displays in the display of X.XXX second line. at 100%. (default is output 0: No Unit frequency) 1: FPM 5~82...
Page 40
Group 16: LCD Function Parameters Group 16: LCD Function Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name RTC Time 0: Hide 16-10 Display 16:Off, 1: Display Setting 17:Off+P1 18:Off+P2, RTC Date 12.01.01 ~ 12.01.0 16-11 19:Off+P1+P2...
Page 41
Group 17: IM Motor Automatic Tuning Group 17: IM Motor Automatic Tuning Parameters Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name 0: Rotational 7: DT Error Auto-tuning 8: Motor 1: Static Auto- Acceleration tuning Error 2: Stator...
Page 42
Group 20 Speed Control Parameters* Group 20 Speed Control Parameters* Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name 20-00 ASR Gain 1 0.00~250.00 3.00 Frequency 1 SLV: ASR Gain 0.500 20-16 Change 0.0~400.0 20-01 Integral 0.001~10.000 PMSLV...
Page 43
Group 22: PM Motor Parameters- Group 22: PM Motor Parameters- only available when PM Control Mode only available when PM Control Mode is selected is selected Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Rated Motor 5: Circuit...
Page 44
Group 23 Pump & HVAC Function Group 23 Pump & HVAC Function Parameters Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name 0: Disable of High Pressure 1: Pump Function 23-20=0 : 0.00 23-00 2: HVAC Selection Minimum...
Page 45
Group 23 Pump & HVAC Function Group 23 Pump & HVAC Function Parameters Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Detection Accumulating) Time of 1: Enable Multiple Electricity 23-30 Pumps in 0.0 ~ 30.0 23-43 Price per 0.000 ~ 5.000...
Page 46
Group 23 Pump & HVAC Function Group 23 Pump & HVAC Function Parameters Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name PID Error Error 23-56 Level of 0 ~ 30 0: Disable Low Suction 1: High Flow Current High...
Page 47
Group 24 Pump Control Function Group 24 Pump Control Function Parameters Parameters Parameter Attribu Parameter Attribu Code Setting Range Default Code Setting Range Default Name Name Cycling. Note1 Bias of 8: Cycle Modes Pump of Inverter Pump Switch 1 to 3 Relay: Pump 0: 1 to 8 pump First on and First...
Chapter 4 LED display Possible solutions Add reactor to power source Troubleshooting and Fault Diagnostics over current Set the longer acceleration 4.1 General time Inverter fault detection and early warning / Replace motor. self-diagnosis function. When the inverter Check the motor wiring.
Page 49
LED display Possible solutions LED display Possible solutions Check and reduce motor load, check and operation External fault duty cycle. (S5) Check V/f curve. Inverter Replace inverter with larger overload rating. Check and reduce motor External fault Multi-function input function ...
LED display Possible solutions When the inverter detected a programming Communication Replace the control board error (for example two parameters contradict Error each other of are set to an invalid setting), the keypad displays a self-diagnostics code. CF01 Note: The fault contact output does not Operator energize on a self-diagnostics error.
Page 51
LED display Possible solutions LED display Possible solutions error (flash) Check under torque under torque detection parameters (08- detection 19 / 08-20). Check load / application. over current Check load and duty cycle protection operation. level B (flash) External baseblock...
Page 52
LED display Possible solutions LED display Possible solutions HFPB Check feedback signal is High flow error correct. Check if feedback value SE01 is lower than limit of Range setting maximum flow. error Check parameter setting. L0PB Check feedback signal is ...
Check if the compressor warning signal appears Archiving Error load used is higher than again, replace the circuit the standard one. board. Contact TECO for more information. PID feedback Control Board Check 23-19 setting. signal loss Error Make sure correct ...
Error Corrective action Increase acceleration Motor time (00-14). acceleration error Disconnect motor (Rotational type load. auto-tuning only). Check the motor tuning data (17-00 to Other auto-tuning 17-09). errors Check motor connection. 4.5 PM Motor Auto-tuning Error When a fault occurs during auto-tuning of a PM motor, the display will show the “IPErr”...
Teco recommends crimp terminals made by NICHIFU for the insulation cap. The table below matches drives models with crimp terminals and insulation caps. Orders can be placed with a Teco representative or directly with the Teco sales department.
Page 95
Fuse Type Drive Model F510 Manufacturer: Bussmann / FERRAZ SHAWMUT Model Fuse Ampere Rating (A) 400 V Class Three-Phase Drives 4001 Bussmann 10CT 690V 10A 4002 Bussmann 10CT 690V 10A 4003 Bussmann 16CT 690V 16A 4005 Bussmann 16CT 690V 16A 4008 Bussmann 25ET 690V 25A...
Page 96
Préface Le produit est un lecteur conçu pour commander un moteur à induction triphasé. lire attentivement ce manuel pour garantir le bon fonctionnement, la sécurité et pour se familiariser avec les fonctions d'entraînement. Le lecteur est un appareil électrique / électronique et doit être installé et géré par un personnel qualifié...
1.2 Câblage Avertissement Coupez toujours l'alimentation électrique avant de procéder à l'installation d'entraînement et le câblage des terminaux utilisateurs. Le câblage doit être effectué par un personnel qualifié / électricien certifié. Assurez-vous que le lecteur est correctement mis à la terre. (220V Classe: impédance ...
pendant que l'alimentation du lecteur est allumé, un choc électrique peut se produire autrement. Ne pas brancher ou débrancher le moteur pendant le fonctionnement. Le variateur pourrai se déclencher et ainsi endommager le lecteur. Les opérations peuvent commencer soudainement si une alarme ou un défaut est réarmé...