Installation and operating instructions, ATS022

5.6 Using pushbuttons in manual mode

Opening/Closing circuit breakers CB1, CB2
In manual mode the circuit breakers can be controlled by means of pushbuttons CB1 and CB2. In case
of a fault, the alarms are activated by the same methods as those for the automatic switching sequence.
Pressing the CB1 key:
• If CB1 is closed, the opening command is sent to CB1
• If CB1 and CB2 are both open, the closing command is sent to CB1
• If CB1 is open and CB2 is closed, no operation is carried out
Pressing CB2 key:
• If CB2 is closed, the opening command is sent to CB2
• If CB2 and CB1 are both open, the closing command is sent to CB2
• If CB2 is open and CB1 is closed, no operation is carried out
Opening/Closing circuit breaker CB3
In manual mode, combination of the UP and DOWN keys allows Opening/Closing of circuit breaker CB3.
• CB3 opening: press the UP and DOWN keys simultaneously for at least 2 seconds.
• CB3 closing: press the UP and DOWN keys simultaneously for at least 2 seconds.
Manual Start/Stop of generator
In manual mode, the combination of the ENTER, CB1 and CB2 keys allows Start/Stop of the generator.
• Generator Start: keeping ENTER pressed, press CB1
• Generator Stop: keeping ENTER pressed, press CB2
1SDH000760R0002
5.
Using the automatic transfer switch
26