5.
Using the automatic transfer switch
Configuration of the System
The system configuration section makes it possible to set:
- The parameters of the two lines
Parameters of lines LN1 - LN2
Rated voltage
Rated frequency
Number of phases LN1
Number of phases LN2
Presence of external voltage
transformer (parameters in the table
Technical data)
Primary voltage TV
Secondary voltage TV
Table 5.4:
Description of parameters of lines ATS022
- Type of application
Type of application
Protection devices
Utilisation of generator
Priority Line
Switching
Table 5.5:
Description of types of application ATS022
1SDH000760R0002
Value
100V/57V– 115V/66V - 120V/70V - 208V/120V
- 220V/127V - 230V/132V -
240V/138V - 277V/160V - 347V/200V -
380V/220V - 400V/230V - 415V/240V -
440V/254V - 480V/277V
50Hz - 60 Hz, 16 2/3 Hz, 400 Hz
1 phase / 3 phases with N / 3 phases without N
1 phase / 3 phases with N / 3 phases without N
absent/present
(for voltages greater than 480VAC)
100V/57V– 115V/66V - 120V/70V - 208V/120V
- 220V/127V - 230V/132V -
240V/138V - 277V/160V - 347V/200V -
380V/220V - 400V/230V - 415V/240V -
440V/254V - 480V/277V - 500V/288V -
550V/317V - 600V/347V - 660V/380V -
690V/400V - 910V/525V - 950V/550V -
1000V/577V - 1150V/660V
100V/57V– 115V/66V - 120V/70V - 208V/120V
- 220V/127V - 230V/132V -
240V/138V - 277V/160V - 347V/200V -
380V/220V - 400V/230V - 415V/240V -
440V/254V - 480V/277V
Value
2CBs / 3CBs NPL opening only / 3CBs NPL
opening&closing / 3CBs NPL BusTie / 3CBs Bus Tie
Generator not in use / Generator in use
Line LN1 / Line LN2 / No priority Line
With inverse procedure/Without inverse procedure
Installation and operating instructions, ATS022
23
Factory settings
400V/230V
50Hz
3 phases with N
3 phases with N
absent
690V/400 V
400V/230 V
Factory settings
2CBs
Generator not in use
Line LN1
With inverse procedure