4. Manual Switch ON Procedures

4.1. First Switch on from Source A

Check that all switches are OFF and check the EPO status.
Connect the mains for source A.
Wait for several seconds until the logic is enabled and the LEDs on the display are switched
ON.
o
Priority LED PS1 or PS2 depending on the default setting.
o
LED S1
o
LED SW1
Connect the mains for source B.
The following LEDs are illuminated:
o
Priority LED PS1 or PS2 depending on the default setting.
o
LED S1
o
LED S2
o
LED SW1 or SW2 according to the primary source

4.2. First Switch on from Source B

Check that all switches are OFF and check the EPO status.
Input the mains for source B.
Wait for several seconds until the logic is enabled and the LEDs on the display are switched ON.
o
Priority LED PS1 or PS2 depending on the default setting.
o
LED S2
o
LED SW2
Connect the mains for source A.
The following LEDs are illuminated:
o
Priority LED PS1 or PS2 depending on the default setting.
o
LED S1
o
LED S2
o
LED SW1 or SW2 according to the primary source

4.3. Switch OFF

WHEN THIS PROCEDURE IS CARRIED OUT THE LOAD IS NO LONGER SUPPLIED BY THE
ATS-16 A.