ABB ATS022 Installation And Operating Instructions Manual page 36

Automatic transfer switch
Table of Contents

Advertisement

Installation and operating instructions, ATS022
Connectors Description
X11:1
Normal Line LN1: L1
X11:2
Normal Line LN1: L2
X11:3
Normal Line LN1: L3
X11:4
Normal Line LN1: N
X12:1
Emergency Line LN2: L1
X12:2
Emergency Line LN2: L2
X12:3
Emergency Line LN2: L3
X12:4
Emergency Line LN2: N
X41:1
+ Auxiliary power supply
X41:2
- Auxiliary power supply
X21:1
Com
X21:2
CB1 opening command
X21:3
CB1 closure command
X22:1
Com
X22:2
CB2 opening command
X22:3
CB2 closure command
X23:1
generator start/stop command
X23:2
Com
X23:3
generator start/stop command
X24:1
CB3 opening command
X24:2
Com
X24:3
CB3 closure command
X29:1
ATS022 unit alarm indication
X29.2
Load protection device
X29:3
not used
circuit breakers command alarm
X29:4
indication
X29.5
automatic/manual mode indication DO10
X29:6
logic enabled/disabled indication
X29:7
Com
X31:1
logic enabling input
X31:2
CB1 status input
X31:3
CB2 status input
X31:4
Com
X32:1
CB3 status input
X32.2
programmable input
X32:3
switching forcing input
X32:4
generator alarm input
1SDH000760R0002
DI/DO
-
-
-
-
-
-
-
-
-
-
-
DO1
DO2
-
DO3
DO4
D05
Open =gen stop; Closed = gen start
-
D05
Closed =gen stop; Open = gen start
D011
-
D011
DO6
Open = no alarm; Closed = alarm
DO7
Open = no alarm; Closed = alarm
DO8
DO9
Open = Automatic;
Open = logic enabled;
DO12
Closed = logic disabled
-
Open = logic disabled;
DI3
Closed = logic enabled
DI1
0=CB open; I=CB closed
DI2
0=CB open; I=CB closed
-
DI11
0=CB open; I=CB closed
DI10
DI9
DI8
36
6.
Input and output signals
Type
-
-
-
-
-
-
-
-
-
-
-
NO
NO
-
NO
NO
-
NO
-
NC
-
Open = no alarm;
Closed = alarm
Closed = Manual
-
-
NO/NC
NO
NO/NC

Hide quick links: