Installation and operating instructions, ATS022
Device configuration
The device configuration section makes it possible to set:
- Limit thresholds
Limit thresholds
Min/max voltage
threshold
Min/max frequency
threshold
Table 5.6:
Description of limit thresholds ATS022
- Time delays
Time delays
TS Delay
TBS Delay
TCE Delay
TCN Delay
TC Delay
TGOFF Delay
TL Delay
Table 5.7:
Description of time delays ATS022
- Digital inputs
Digital Input
Digital Input DI10 - function
Digital Input DI10 - type
Digital Input DI8 - type
Table 5.8:
Description of inputs ATS022
- Modbus parameters
Modbus
Modbus Address
Modbus Baud Rate
Modbus Stop Bits
Modbus Parity
mode
Table 5.9:
Description of Modbus parameters ATS022
- Language and backlit display
Function
Backlighting duration
Language
Table 5.10:
Description of language and backlighting ATS022
1SDH000760R0002
Value
-30% ...-5%, +5% ... +30%, step ± 1%
(Imbalance of voltage set at same threshold)
-10% ...-1%, +1% ... +10%, step ± 1%
Value
0...30s, step 1s
0...59s, , step 1s, 1,2,3...30min, step 1min
0...60s, step 1s
0...60s, step 1s
0...60s, step 1s
0...59s, , step 1s, 1,2,3...30min, step 1min
0...60s, step 1s
Value
disabled/generator start/logic enabling/remote
reset/EMERGENCY BLOCK
NO/NC
NO/NC
Value
1...247
9600/19200/38400 bps
0,1
even, odd, absent
local, remote
Value
Always On, 0...59s, step 1s, 1,2,3...30min, step 1min Always On
English/Italian/German/French/Spanish/Finnish/
Russian/Chinese
5.
Using the automatic transfer switch
24
Factory settings
-15%; +15%
-1%; +1%
Factory settings
0s
0s
3s
3s
3s
5s
0s
Factory settings
Generator Start
NO
NO
Factory settings
1
9600
1
absent
local
Factory settings
English