Holding Position; Input A Jumper; Input B Jumper; C/D Input Jumper - Siemens SIMATIC TI505 User Manual

High speed counter encoder module
Hide thumbs Also See for SIMATIC TI505:
Table of Contents

Advertisement

Holding Position

1 s Jumper

Input A Jumper

Input B Jumper

C/D Input Jumper

Counter 3/2/6/5
Output Jumper
High Speed Counter Encoder Module User Manual
NOTE: Select two input jumpers from the following list. Select one jumper to
clock the counter and one jumper (or none) to gate the counter.
The holding position simply stores the jumper until needed.
The 1 s jumper selects a 1 s internal signal to clock the counter; the gate
position is not applicable for this jumper.
Input A jumper connects this signal to clock or gate/trigger the 16-bit
counter.
Input B jumper connects this signal to clock or gate/trigger the 16-bit
counter.
The C (for counters 2 and 5) or D (for counters 3 and 6) Input jumper allows
you to select this input to clock or gate the counter. Clock is the default
position.
You can jumper the output from counter 3 into counter 2 to either clock or
gate the counter.
You can jumper the output from counter 2 into counter 3 to either clock or
gate the counter.
You can jumper the output from counter 6 into counter 5 to either clock or
gate the counter.
You can jumper the output from counter 5 into counter 6 to either clock or
gate the counter.
Optional Configurations
5-17