16-Bit Prescale 24-Bit Counting - Siemens SIMATIC TI505 User Manual

High speed counter encoder module
Hide thumbs Also See for SIMATIC TI505:
Table of Contents

Advertisement

Prescale Counting Applications (continued)
16-Bit Prescale
24-Bit Counting
A-8
Applications
The 16-bit prescale 24-bit counting mode cascades the output of one 16-bit
counter, in Divide-by-N mode, into the A input of the same channel's 24-bit
counter. The B input jumper is set for Up Count Only.
By using the repetitive nature of Divide-by-N mode, the output of the 16-bit
counter pulses the rollover signal, at every count of 1, into clock input A of
the 24-bit counter. The output of the 16-bit counter is not controlled by the
Force Output On bit (WY19.09, .10, .13, or .14).
16-Bit Counter (2, 3, 5, or 6) Configuration:
Channel Count Format:
Counter Preset Value:
Counter Mode:
Internal Gate:
External Gate:
24-Bit Counter (1 or 4) Configuration:
Preset:
Internal Inhibit:
Internal Reset:
Initial Output:
After programming, the 24-bit counter value is zero. On the first valid clock
pulse, the 16-bit counter is set to the preset value. The clock decrements the
count until the count value reaches 1. During the next clock pulse the
output turns On generating a carry into the 24-bit counter. The 16-bit
preset is loaded, and counting continues with each clock. The carry is
generated every preset number of clocks. Setting the 16-bit Reset flag
pauses the counting. Clearing the flag reloads the preset value after the
first valid clock.
Down Counting.
Unsigned Integer, 0 to 65535
prescale value to divide clock pulses
Divide-by-N.
Reset Flags, WY19.03, .04, .07, .08.
Use the RESET or INHIBIT signal.
Per application.
Reset Flags, WY19.01, .05.
Reset Flags, WY19.02, .06.
Off.
High Speed Counter Encoder Module User Manual

Advertisement

Table of Contents
loading

Table of Contents