2.7

Communication connectors and terminals

2.7.1
PU connector
Mounting the operation panel or parameter unit on the enclosure surface
• Having an operation panel or a parameter unit on the enclosure surface is convenient. With a connection cable, the
operation panel or the parameter unit can be mounted to the enclosure surface and connected to the inverter.
Use the option FR-CB2[ ], or connectors and cables available on the market.
(To install the operation panel, the optional connector (FR-ADP) is required.)
Securely insert one end of the connection cable until the stoppers are fixed.
Parameter unit (FR-PU07)
(option)
NOTE
• Refer to the following table when fabricating the cable on the user side. Keep the total cable length within 20 m.
• Commercially available products (as of February 2015)
Name
SGLPEV-T (Cat5e/300 m)
Communication cable
24AWG  4P
RJ-45 connector
5-554720-3
Communication operation
• Using the PU connector enables communication operation from a personal computer, etc. When the PU connector is
connected with a personal, FA or other computer by a communication cable, a user program can run to monitor the inverter
or read and write parameters.
Communication can be performed with the Mitsubishi inverter protocol (computer link operation).
(For details, refer to the FR-A800 Instruction Manual (Detailed).)
Parameter unit connection cable
(FR-CB2[ ]) (option)
Operation panel (FR-DU08)
Operation panel connection
connector (FR-ADP)
(option)
Operation panel (FR-LU08)
(option)
Model
Mitsubishi Cable Industries, Ltd.
Tyco Electronics
Communication connectors and terminals
Manufacturer
INSTALLATION AND WIRING
2
51