Mitsubishi Electric A800-GF Instruction Manual page 41

Hide thumbs Also See for A800-GF:
Table of Contents

Advertisement

Control circuit
2.6.2
Details on the control circuit terminals of the
converter unit (FR-CC2)
The input signal function of the terminals in
function selection).
For the parameter details, refer to the FR-CC2 Instruction Manual.
Input signal
Terminal
Terminal name
symbol
RES
Reset
External thermal
OH
relay input
RDI
Contact input
Contact input
common (sink)
External transistor
SD
common (source)
24 VDC power supply
common
External transistor
common (sink)
PC
Contact input
common (source)
24 VDC power supply
common
24 V external power
+24
supply input
40
INSTALLATION AND WIRING
can be selected by setting Pr.178, Pr.187, Pr.189 to Pr.195 (I/O terminal
Terminal function description
Use this signal to reset a fault output provided when a protective function
is activated. Turn ON the RES signal for 0.1 s or longer, then turn it OFF.
In the initial setting, reset is always enabled. By setting Pr.75, reset can
be set enabled only at fault occurrence of the converter unit. The inverter
recovers about 1s after the reset is released.
The external thermal relay input (OH) signal is used when using an
external thermal relay or a thermal protector built into the motor to
protect the motor from overheating.
When the thermal relay is activated, the inverter trips by the external
thermal relay operation (E.OHT).
The function can be assigned by setting Pr.178.
Common terminal for contact input terminal (sink logic) and terminal FM
Connect this terminal to the power supply common terminal of a
transistor output (open collector output) device, such as a programmable
controller, in the source logic to avoid malfunction by undesirable
current.
Common terminal for the 24 VDC power supply (terminal PC, terminal
+24)
Isolated from terminals 5 and SE.
Connect this terminal to the power supply common terminal of a
transistor output (open collector output) device, such as a programmable
controller, in the source logic to avoid malfunction by undesirable
current.
Common terminal for contact input terminal (source logic).
Can be used as a 24 VDC 0.1 A power supply.
For connecting a 24 V external power supply.
If a 24 V external power supply is connected, power is supplied to the
control circuit while the main power circuit is OFF.
Rated
specification
Input resistance
4.7 k
Voltage when
contacts are open:
21 to 27 VDC
When contacts are
short-circuited:
4 to 6 mADC
———
Power supply voltage
range 19.2 to 28.8
VDC
Permissible load
current 100 mA
Input voltage 23 to
25.5 VDC
Input current 1.4 A or
less

Advertisement

Table of Contents
loading

Table of Contents