Communication connectors and terminals
2.7.2
CC-Link IE Field Network function
CC-Link IE Field Network communication specifications
Item
Transmission speed
Communication method
Number of units connected
Maximum distance between
nodes
Maximum number of
branches
Topology
Connection cable
Connector
Node type
Parts
NOTE
• Do not remove the CC-Link IE Field Network communication circuit board or the earth plate.
Connection cable
For wiring, use the 1000BASE-T compliant Ethernet cables.
Ethernet cable
Category 5e or higher
(Double shielded/STP) Straight cable
NOTE
• For CC-Link IE Field Network wiring, use the recommended wiring components by CC-Link Partner Association.
• Cables for CC-Link IE Controller Network cannot be used for CC-Link IE Field Network.
• Some cable connector shapes are not compatible with CC-Link IE Field Network communication connector.
52
INSTALLATION AND WIRING
1 Gbps
Token passing
120 units at max. (64 units when all stations are inverters handling 128-word transmissions.)
Different devices can be connected together.
100 m
No upper limit within the same Ethernet system
Line, star, ring, or a combination of line and star
Ethernet cable
(IEEE 802.3 1000BASE-T compliant cable or ANSI/TIA/EIA-568-B (Category 5e) compliant shielded 4-pair
branched cable)
Shielded RJ-45
Intelligent device station
RUN D LINK
SD ERR
RD L.ERR
RJ-45 connector
Description
Maximum cyclic size (of one node)
CC-Link IE Field Network communication
circuit board
Operation status indication LED
Connector for communication (PORT2)
Connector for communication (PORT1)
Earth plate
Connector
The following conditioning cables:
IEEE802.3 (1000BASE-T)
ANSI/TIA/EIA-568-B (Category 5e)
RX
64 bits
RY
64 bits
RWr
128 words
RWw
128 words
Type