Black Start Function - Ingeteam 1PLAY Quick Start Manual

Ingecon sun storage
Table of Contents

Advertisement

3 Black start function

This chapter describes how to turn on the system when the PV energy is not available, and the battery is the
only source to turn on the inverter.
To do so, once all the previous steps have been completed, the following steps must be followed:
1) Make sure that the battery circuit breaker is in OFF position.
2) Move the circuit breaker to ON position, press and hold the red start button for 5 seconds to turn the
battery pack on.
3) After 30 seconds press and hold the red start button again for another 5 seconds.
4) Then the inverter and battery should get powered. Make sure that the display´s screen is ON.
In this situation, if the battery does not receive communication from the inverter for 10 minutes, its internal
circuit breaker will be opened.
This period time is enough to do the first commissioning of the system as update the correct inverter´s
firmware and select the correct battery type.
Technical Guide
19/11/2020
INGECON SUN STORAGE 1Play
5/11

Advertisement

Table of Contents
loading

Table of Contents