7 Trouble shooting

The inverter receives battery´s alarms from BMS and reacts different for each alarm.
Inverter notifies via Interface Web when battery is in alarm status:
Also, the inverter shows the alarm:
The reaction of the inverter for each alarm is:
Inverter Alarm Name
0x0001
High Current Charge
0x0080
High Current Discharge
0x0002
High Voltage
0x0004
Low Voltage
0x0008
High Temperature
Technical Guide
Battery Protection Name
COC: Charge Over Current Protect
DOC: Discharge Over Current Protect
BOV: Single Cell Over Voltage Protect
POV:
Charge
system
Protect
MOV: Module Over Voltage Protect
BUV: Single Cell Under Voltage Protect
PUV: Discharge system Under Voltage
Protect
MUV: Module Under Voltage Protect
COT: Charge Cell Over Temperature
Protect
DOT: Discharge Cell Over Temperature
Protect
19/11/2020
INGECON SUN STORAGE 1Play
Inverter Reaction
Stop battery charge
Stop battery discharge
Over
Voltage
Stop battery charge
Stop battery discharge
In on-grid, stop battery
charge & discharge.
In off-grid, stop inverter.