Installation; Unpacking; Panel Mounting - FlowLine DataLoop LI25 Series Instruction Manual

Hide thumbs Also See for DataLoop LI25 Series:
Table of Contents

Advertisement

DataLoop™ LI25 Level Controller

INSTALLATION

There is no need to remove the meter from its case to complete the installation,
wiring, and setup of the meter.

Unpacking

Remove the meter from box. Inspect the packaging and contents for damage.
Report damages, if any, to the carrier.
If any part is missing or the meter malfunctions, please contact your supplier or
the factory for assistance.

Panel Mounting

Prepare a standard 1/8 DIN panel cutout – 3.622" x 1.772" (92 mm x
45 mm). Refer to Mounting Dimensions, page 23 for more details.
Clearance: allow at least 4" (102 mm) behind the panel for wiring.
Panel thickness: 0.04" - 0.25" (1.0 mm - 6.4 mm).
Minimum steel/stainless steel panel thickness to maintain watertight rating:
0.06" (1.5 mm).
Note: A steel or stainless steel panel rather than plastic is
recommended in cases where a watertight or dust-tight seal is
required between the meter and the panel.
Remove the two mounting brackets provided with the meter (back-off the two
screws so that there is ¼" (6.4 mm) or less through the bracket. Slide the
bracket toward the front of the case and remove).
Insert meter into the panel cutout.
Install mounting brackets and tighten the screws against the panel. To
achieve a proper seal, tighten the mounting bracket screws evenly until
meter is snug to the panel along its short side. DO NOT OVER TIGHTEN,
as the rear of the panel may be damaged.
8
Instruction Manual
MN301034 rev D