DataLoop™ LI25 Level Controller
4-20 MA INPUT CONNECTIONS
Input connections are made to a four-terminal connector labeled S+|S-|B+|B-.
The loop-powered backlight is an optional configuration and requires a total
maximum voltage drop of 5.7 V. The backlight is recommended for dim lighting
conditions and is enabled when wired as shown in Figure 3. It may be
bypassed if installed in bright lighting conditions to reduce the maximum
voltage drop to 2.0 V as shown in Figure 4.
Power
Supply
Figure 3. Input Connections with Backlight
Power
Supply
Figure 4. Input Connections without Backlight
MN301034 rev D
4-20 mA
Transmitter
4-20 mA
Transmitter
Instruction Manual
S+ S- B+ B-
S+ S- B+ B-
11