1MRS757807 B
2.3.9.3
Table 93:
LD0.XGGIO120 Physical I/O
IEC 61850 name
LD0.XGGIO120
.Ind1.stVal
.Ind2.stVal
.Ind3.stVal
.Ind4.stVal
2.3.10
2.3.10.1
Table 94:
LD0.ATSABTC1 Automatic transfer switch (1)
IEC 61850 name
LD0.ATSABTC1
.OpOpn1.general
.OpCls1.general
.OpOpn2.general
.OpCls2.general
.TrnBlkAlm.stVal
.PrgAuto.stVal
2.4
Remote Monitoring and Control REC615
Point List Manual
LD0.XGGIO120 Physical I/O
SA name
-
-
-
-
Automation functions
LD0.ATSABTC1 Automatic transfer switch (1)
SA name
OPEN_CB1
CLOSE_CB1
OPEN_CB2
CLOSE_CB2
BLKD_AL
INPRO
Binary outputs
Table 95:
Explanations of the binary output table columns
Column name
Description
IEC 61850
Original IED data object identification. Described in the IEC 61850 format as
name
Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical
Node is the same as the application function block name.
SA name
The signal may have a defined label that is visible, for example, in the Application
Configuration tool in PCM600.
Description
Short description of the signal. See the technical manual for more information.
Type
Output type. Some outputs can only be controlled with value "On". Writing "Off" to
these points does not affect the function of the output. See the DNP3 control relay
output block parameters.
Description
X120-Input 1
X120-Input 2
X120-Input 3
X120-Input 4
Description
CB open cmd for bus 1
CB close cmd for bus 1
CB open cmd for bus 2
CB close cmd for bus 2
ATS blocked alarm
ATS in progress
Section 2
DNP3 data mappings
Values
1/0=ON/OFF
1/0=ON/OFF
1/0=ON/OFF
1/0=ON/OFF
Values
1=Open
1=Close
1=Open
1=Close
1=Alarm
1=In progress
43