Section 2
DNP3 data mappings
2.3.6.35
Table 65:

LD0.FRPFRQ2 Frequency protection (2)

IEC 61850 name
LD0.FRPTRC2
.Str.general
LD0.FRPTOF2
.Op.general
LD0.FRPTUF2
.Op.general
LD0.FRPFRC2
.Op.general
2.3.6.36
Table 66:

LD0.T1PTTR1 Thermal protection (1)

IEC 61850 name
LD0.T1PTTR1
.AlmThm.general
.Op.general
.Str.general
2.3.6.37
Table 67:

LD0.INRPHAR1 Three-phase inrush detection (1)

IEC 61850 name
LD0.INRPHAR1
.Str.general
2.3.6.38
Table 68:

LD0.TRPPTRC1 Global conditioning (1)

IEC 61850 name
LD0.TRPPTRC1
.Op.general
.Tr.general
34
LD0.FRPFRQ2 Frequency protection (2)
SA name
START
OPR_OFRQ
OPR_UFRQ
OPR_FRG
LD0.T1PTTR1 Thermal protection (1)
SA name
ALARM
OPERATE
START
LD0.INRPHAR1 Three-phase inrush detection (1)
SA name
-
LD0.TRPPTRC1 Global conditioning (1)
SA name
-
-
Description
Stage start
Overfrequency
-Operate
Underfrequency
-Operate
Frequency gradient
-Operate
Description
Thermal alarm
General operate
General start
Description
General start
Description
Operate input signal
Trip output signal
Remote Monitoring and Control REC615
1MRS757807 B
Values
1=Start
1=Operate
1=Operate
1=Operate
Values
1=Alarm
1=Operate
1=Start
Values
1=Start
Values
1=Operate
1=Trip
Point List Manual

Advertisement

Table of Contents
loading

Table of Contents