Ld0.Phqvvr1 Voltage Variation Signals (1); Ld0.Vsqvub1 Voltage Unbalance Detection (1); Protection Functions; Ld0.Phlptoc1 Phase Overcurrent Protection, Low Stage (1) - ABB Relion REC615 Manual

Grid automation remote monitoring and control
Hide thumbs Also See for Relion REC615:
Table of Contents

Advertisement

Section 2
DNP3 data mappings
2.3.5.3
Table 29:

LD0.PHQVVR1 Voltage variation signals (1)

IEC 61850 name
LD0.PH1QVVR1
.VarStrGen.stVal
.VarEnd.stVal
.SwlOp.stVal
.DipOp.stVal
.IntrOp.stVal
2.3.5.4
Table 30:

LD0.VSQVUB1 Voltage unbalance detection (1)

IEC 61850 name
LD0.VSQVUB1
.VarStr.stVal
.HiPctVUnb.stVal
2.3.6
2.3.6.1
Table 31:

LD0.PHLPTOC1 Phase overcurrent protection, low stage (1)

IEC 61850 name
LD0.PHLPTOC1
.Op.general
.Str.general
2.3.6.2
Table 32:

LD0.PHHPTOC1 Phase overcurrent protection, high stage (1)

IEC 61850 name
LD0.PHHPTOC1
.Op.general
.Str.general
26
LD0.PHQVVR1 Voltage variation signals (1)
SA name
-
-
-
-
-
LD0.VSQVUB1 Voltage unbalance detection (1)
SA name

Protection functions

LD0.PHLPTOC1 Phase overcurrent protection, low stage (1)
SA name
OPERATE
START
LD0.PHHPTOC1 Phase overcurrent protection, high stage (1)
SA name
OPERATE
START
Description
Variation event detected
Variation event ended
Swell event detected
Dip event detected
Interruption event detected
Description
Event start
Unbalance exceeds limit
Description
Stage operate
Stage start
Description
Stage operate
Stage start
Remote Monitoring and Control REC615
1MRS757807 B
Values
1=Detected
1=Ended
1=Detected
1=Detected
1=Detected
Values
1=Start
1=Exceeds
Values
1=Operate
1=Start
Values
1=Operate
1=Start
Point List Manual

Advertisement

Table of Contents
loading

Table of Contents