VESDA Sensepoint XCL – Large Bore Installation Manual
Modbus
Information
Register
Address
40114
Relay Fitted
40115
BLE Fitted
40116
Reserved
40117
Temperature (°C)
40118 to
Reserved
40122
40123 to
Date and Time
40131
40132
Sensor Technology
40133 to
Gas reading (by status) R
40134
40135 to
Reserved
40136
40137 to
Microcontroller
40138
Operating Voltage
40139 to
Microcontroller
40140
Reference Voltage
40141
BLE Connection Status R
40142 to
Reserved
40145
41
R/W
Type
Size
R
u16
1
R
u16
1
R
u16
1
R
s16
1
Transmitter temperature
R
string[18] 9
Format is "mm/dd/yy hh:mm:ss"
R
u8
1
Sensor type only, not a specific gas type
f32
2
Gas reading value calculated by device status (i.g
negative value in fault status )
1. If device is in Inhibit state, return value is base
concentrate of sensor data (In case of ECC,
Noramlly 0)
2. If device is in fault state, return value is :
3. return = f32_gas_full_scale / 16 * (fault current
value of configuration - 4.0);
4. If device is in warning state, return value is : return
= f32_gas_full_scale / 16 * (warning current value
of configuration - 4.0);
R
f32
2
Operating voltage of MCU
R
f32
2
Reference voltage
u8
1
Connection status with BLE module
Description
0x00: Relay not fitted, 0x01: Relay fitted
0x00: BLE not fitted, 0x01: BLE fitted
same as '30035 to 30036'
0x00: Not connected, 0x01: Connected
Notes
0x00 :ECC
l
0x01: FL CAT
l
0x02: IR
l
0x03: PID (not in use)
l
0x04: MOS (not in use)
l
VESDA
www.xtralis.com